Plan Review Notes
Plan Review Notes For Permit 19020191
Permit Number 19020191
Review Stop E
Sequence Number 1
Notes
Date Text
2019-03-19 12:24:39ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SUBMIT A LOAD CALCULATIONS FOR ALL THE MAINS
 INCLUDING THE GENERATOR, ALL RISER PANELS AND
 DISTRIBUTION SWITCHBOARDS.
  
 2) NEED THE AIC RATINGS FOR ALL RISER QUIPMENT 110.10,
 110.14
  
 110.24 AVAILABLE FAULT CURRENT
 ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING
 UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE
 MAXIMUM
 AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL
 INCLUDE THE DATE
 THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF
 SUFFICIENT
 DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
  
 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT
 CURRENT RATINGS, AND OTHER CHARACTERISTICS
 THE OVERCURRENT PROTECTIVE DEVICES, THE TOTAL
 IMPEDANCE, THE
 EQUIPMENT SHORT-CIRCUIT CURRENT RATINGS, AND OTHER
 CHARACTERISTICS
 OF THE CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND
 COORDINATED
 TO PERMIT THE CIRCUIT PROTECTIVE DEVICES USED TO CLEAR
 A FAULT TO DO
 SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT
 OF THE
 CIRCUIT.
  
 3) FOUND REFERENCES TO A BAS SYSTEM?
  
 4) SOME OF THE PANELS USED 50% ON LOADS THAT DID NOT
 MEET THE 50% RULE IN 220.44.
  