| Plan Review Notes For Permit 19020191 |
| Permit Number |
19020191 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-19 12:24:39 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NEED TO SUBMIT A LOAD CALCULATIONS FOR ALL THE MAINS | | | INCLUDING THE GENERATOR, ALL RISER PANELS AND | | | DISTRIBUTION SWITCHBOARDS. | | | | | | 2) NEED THE AIC RATINGS FOR ALL RISER QUIPMENT 110.10, | | | 110.14 | | | | | | 110.24 AVAILABLE FAULT CURRENT | | | ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN | | | DWELLING | | | UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE | | | MAXIMUM | | | AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL | | | INCLUDE THE DATE | | | THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF | | | SUFFICIENT | | | DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. | | | | | | 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT | | | CURRENT RATINGS, AND OTHER CHARACTERISTICS | | | THE OVERCURRENT PROTECTIVE DEVICES, THE TOTAL | | | IMPEDANCE, THE | | | EQUIPMENT SHORT-CIRCUIT CURRENT RATINGS, AND OTHER | | | CHARACTERISTICS | | | OF THE CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND | | | COORDINATED | | | TO PERMIT THE CIRCUIT PROTECTIVE DEVICES USED TO CLEAR | | | A FAULT TO DO | | | SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT | | | OF THE | | | CIRCUIT. | | | | | | 3) FOUND REFERENCES TO A BAS SYSTEM? | | | | | | 4) SOME OF THE PANELS USED 50% ON LOADS THAT DID NOT | | | MEET THE 50% RULE IN 220.44. | | | |
|