| Date |
Text |
| 2019-03-21 10:09:25 | FBC SIXTH EDITION (2017) - BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020191 |
| | ADD: 351 PEMBROKE PLACE |
| | CONT: HEDRICK BROTHERS |
| | TEL: |
| | E-MAIL: |
| | CONST. TYPE: 1-B |
| | OCC. TYPE: R-2 W/ A3 & B ACCESSORY OCC. |
| | SPRINKLERED |
| | |
| | 1ST REVIEW |
| | DATE: |
| | ACTION: DENIED |
| | |
| | 1) ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| | DEVELOPMENT. |
| | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR @ |
| | 561- 822-1515 OR EMAIL: [email protected] |
| | |
| | 2) BASED ON THE LATEST ICC VALUATION DATA, THE VALUE |
| | FOR THE CONSTRUCTION OF $23,760,506.00 IS LOW. THE |
| | CALULATED VALUE FOR THE BUILDING IS $26,297,570.00. FBC |
| | 109.3 BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL EFFECTIVELY BE THE VALUE OF THE |
| | BUILDING THAT THE PERMIT FEES WILL BE BASED ON FOR THIS |
| | PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO |
| | COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT |
| | COVERED UNDER THE PRIME OR MASTER PERMIT. |
| | |
| | 3) THE REQUIREMENTS FOR THRESHOLD BUILDINGS APPLY TO |
| | THIS BUILDING. |
| | THRESHOLD BUILDING / FL S. S. 553.71(7) "THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | A) FBC (CITY AMENDMENTS) 110.8.1 THRESHOLD INSPECTION |
| | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE. |
| | |
| | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 4) ON PAGE 026, SHEET S000, ASCE 7-16 IS INCORRECTLY |
| | SPECIFIED. CHAPTER 35 OF THE 2017 FBC REFERENCES ASCE |
| | 7-10. |
| | |
| | 5) ON PAGE 005, SHEET G100, THE 2015 FBC IS SPECIFIED |
| | AND THIS PROJECT IS UNDER THE 2017 FBC. |
| | |
| | 6) ON PAGE 005, SHEET G100, THE CODE SECTIONS ARE |
| | SPECIFIED AS IBC 2015 RATHER THAN FBC 2017. |
| | |
| | 7) BASED ON THE SURVEY THAT WAS SUBMITTED THER ARE TWO |
| | BUILDINGS ON THE SAME LOT THAT ARE ADJACENT TO THE |
| | PROPOSED BUILDING WHICH WILL REQUIRE AN IMAGINARY LINE |
| | TO BE ESTABLISHED BETWEEN THE BUILDINGS TO DETERMINE |
| | THE FIRE SEPARATION DISTANCE. THE FIRE SEPARATION |
| | DISTANCE IS REQUIRED IN ORDER TO DETERMINE THE EXTERIOR |
| | WALL, AREA OF OPENINGS PERMITTED AND OPENING |
| | PROTECTIONS. THE EXISTING BUILDINGS WILL HAVE TO |
| | COMPLY, AS WELL AS, THE PROPOSED BUILDING. PROVIDE |
| | PLANS AND CALCULATIONS TO SHOW COMPLIANCE. FBC |
| | 107.2.1.2 |
| | |
| | FBC 705.3 BUILDINGS ON THE SAME LOT. |
| | |
| | FOR THE PURPOSES OF DETERMINING THE REQUIRED WALL AND |
| | OPENING PROTECTION, PROJECTIONS AND ROOF-COVERING |
| | REQUIREMENTS, BUILDINGS ON THE SAME LOT SHALL BE |
| | ASSUMED TO HAVE AN IMAGINARY LINE BETWEEN THEM. |
| | |
| | WHERE A NEW BUILDING IS TO BE ERECTED ON THE SAME LOT |
| | AS AN EXISTING BUILDING, THE LOCATION OF THE ASSUMED |
| | IMAGINARY LINE WITH RELATION TO THE EXISTING BUILDING |
| | SHALL BE SUCH THAT THE EXTERIOR WALL AND OPENING |
| | PROTECTION OF THE EXISTING BUILDING MEET THE CRITERIA |
| | AS SET FORTH IN SECTIONS 705.5 AND 705.8. |
| | |
| | 8) THERE IS A 6' FPL UTILITY EASEMENT SHOWN ON THE |
| | SURVEY AT THE NORTH EAST END OF THE PROPOSED BUILDING |
| | THAT IS WITHIN THE FOOTPRINT OF THE STRUCTURE. EXPLAIN |
| | HOW THIS ISSUE WILL BE RESOLVED. FBC 107.2.1 |
| | |
| | 9) FBC 713.13.4 REQUIRES THE TRASH CHUTE DISCHARGE ROOM |
| | TO BE SEPARATED BY FIRE BARRIERS WITH A FIRE-RESISTANCE |
| | RATING NOT LESS THAN THE REQUIRED FIRE RATING OF THE |
| | SHAFT ENCLOSURE WHICH IS TWO HOURS. OPENINGS INTO THE |
| | DISCHARGE ROOM FROM THE REMAINDER OF THE BUILDING SHALL |
| | BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE |
| | PROTECTION RATING EQUAL TO THE PROTECTION REQUIRED FOR |
| | THE SHAFT ENCLOSURE. DOORS SHALL BE SELF- OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 716.5.9.3. |
| | |
| | 10) ON SHEETS 007-G111 AND 008-G113, THE LIFE SAFETY |
| | PLANS ARE NOT COMPLETE. THE EXIT TRAVEL DISTANCE FOR |
| | THE WEST SIDE OF THE BUILDING DOES NOT EXTEND TO THE |
| | INTERIOR EXIT STAIRSWAY AND THERE IS NOT ONE SHOWN FOR |
| | THE EAST END. THE EXITING INFORMATION IS NOT PROVIDED |
| | FOR THE OFFICE AND MUTIPURPOSE AREAS. FBC 107.2.1 |
| | SHOW THE FOLLOWING ON THE LIFE SAFETY PLANS: |
| | A) COMMON PATH OF EGRESS TRAVEL (FBC 1006.2.1) |
| | B) EXIT SEPARATION DISTANCE (FBC 1007.1) |
| | C) REQUIRED AND PROVIDED EGRESS STAIRWAY WIDTHS (FBC |
| | 1005.3.1) |
| | D) REQUIRED AND PROVIDED EGRESS CORRIDOR WIDTHS (FBC |
| | 1005.3.2) |
| | |
| | 11) ON SHEET 007-G111, IT APPEARS THAT THE DOOR TO THE |
| | CENTRAL STAIRWAY LOCATED ON THE GROUND FLOOR THAT |
| | SWINGS INTO THE CORRIDOR MAY REDUCE THE REQUIRED EGRESS |
| | WIDTH BY MORE THAN ONE - HALF, WHICH IS NOT ALLOWED BY |
| | FBC 1005.7.1. |
| | |
| | 12) ON SHEET 007-G111 IT APPEARS THAT THE WALL AND DOOR |
| | LOCATED IN THE EAST AND WEST EGRESS CORRIDORS WILL NOT |
| | COMPLY WITH FBC 1005.4 CONTINUITY. THE MINIMUM WIDTH OR |
| | REQUIRED CAPACITY OF THE MEANS OF EGRESS REQUIRED FROM |
| | ANY STORY OF A BUILDING SHALL NOT BE REDUCED ALONG THE |
| | PATH OF EGRESS TRAVEL UNTIL ARRIVAL AT THE PUBLIC WAY. |
| | |
| | 13) ON SHEET 30, S011 THE ROOF COMPONENT AND CLADDING |
| | PRESSURES IN THE CHART ARE THE SAME FOR ROOF ZONES 2 |
| | AND 3. THE ROOF DIAGRAM DOES NOT SPECIFY THAT THE |
| | CORNERS OF THE BUILDING ARE ZONE 3. THE BUILDING IS |
| | REQUIRED TO HAVE A CONTINOUS 3' HIGH PARAPET AROUND THE |
| | ROOF IN ORDER TO USE ZONE 2 PRESSURES FOR ZONE 3 PER |
| | ASCE 7-10. PLEASE CLARIFY. FBC 1507 & 1609.2 |
| | |
| | 14) IN ADDITION TO THE ADA COMPLIANT RESIDENTIAL UNITS, |
| | PROVIDE PLANS WHICH SHOW THAT THE REMAINING APARTMENTS |
| | COMPLY WITH FAIR HOUSING ACCESSIBILITY GUIDELINES. FBC |
| | ACCESSIBILITY SECTION 224.7 & FAIR HOUSING GUIDELINES, |
| | SEE PLUMBING COMMENTS. |
| | |
| | 15) A SITE PLAN THAT SPECIFIES THE TOTAL NUMBER AND |
| | LOCATION OF REQUIRED PARKING SPACES, THE NUMBER AND |
| | LOCATION OF REQUIRED ADA COMPLIANT CAR AND VAN PARKING |
| | SPACES, PROVIDE ELEVATIONS OF THE ADA PARKING AREA AND |
| | THE ACCESSIBLE ROUTE TO THE BUILDING. FBC ACCESSIBILITY |
| | SECTION 502 |
| | |
| | 16) SIGNED AND SEALED ENERGY CALCULATIONS ARE REQUIRED |
| | TO BE SUBMITTED. FS 471 AND FAC 61G 15-23 |
| | |
| | 17) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER |
| | FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| | COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| | INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| | PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS, |
| | WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR |
| | DOOR TYPES. |
| | THE FOLLOWING ITEMS REQUIRE PRODUCT APPROVALS: |
| | (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 18) IDENTIFY GLAZING/ MULLIONS. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 19) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 20) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER OR REGISTERED |
| | ARCHITECT. 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 21) BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING. |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 22) 1609.1.2 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, GLAZED OPENINGS IN |
| | BUILDINGS SHALL BE IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT-RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF ANSI/DASMA 115 (FOR GARAGE DOORS AND ROLLING DOORS) |
| | OR TAS 201, 202 AND 203, AAMA 506, ASTM E1996 AND ASTM |
| | E1886 REFERENCED HEREIN, OR AN APPROVED |
| | IMPACT-RESISTANT STANDARD AS FOLLOWS: |
| | |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET (9144 MM) OF |
| | GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE |
| | TEST OF ASTM E1996. |
| | |
| | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9144 MM) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST OF ASTM E1996. |
| | |
| | 23) 1609.1.2.1 LOUVERS. |
| | LOUVERS PROTECTING INTAKE AND EXHAUST VENTILATION DUCTS |
| | NOT ASSUMED TO BE OPEN THAT ARE LOCATED WITHIN 30 FEET |
| | (9144 MM) OF GRADE SHALL MEET THE REQUIREMENTS OF AMCA |
| | 540 OR SHALL BE PROTECTED BY AN IMPACT-RESISTANT COVER |
| | COMPLYING WITH THE LARGE MISSILE TEST OF ASTM E1996 OR |
| | AN APPROVED IMPACT-RESISTANCE STANDARD. LOUVERS |
| | REQUIRED TO BE OPEN FOR LIFE SAFETY PURPOSES SUCH AS |
| | PROVIDING A BREATHABLE ATMOSPHERE SHALL MEET THE |
| | REQUIREMENTS OF AMCA 540. |
| | |
| | 24) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |