| 2020-08-21 15:57:31 | INCOMPLETE APPLICATION |
| | |
| | PERMIT 19020053 - MCIMETRO PROJECT #:1801CVFF.210 |
| | UNDERGROUND FIBER CLARE TO CLEMATIS - 3RD REVIEW |
| | |
| | PLEASE SEE THE LIST BELOW FOR AN ANALYSIS OF THE |
| | DEFICIENCIES IN INFORMATION REQUIRED BY SECTION 78-401 |
| | OF THE CITY OF WEST PALM BEACH CODE AS PART OF THE |
| | COMMUNICATION FACILITIES PLACEMENT PERMIT APPLICATION. |
| | THE DEFICIENT INFORMATION MUST BE PROVIDED FOR STAFF TO |
| | REVIEW THE PERMIT APPLICATION. PLEASE NOTE THAT STAFF |
| | HAS ALSO INCLUDED SOME SUBSTANTIVE REVIEW COMMENTS, |
| | THAT WHILE NOT RESULTING IN A DEFICIENT APPLICATION, |
| | NEED TO BE ADDRESSED OR THE PERMIT WILL NOT BE |
| | APPROVED. |
| | |
| | 1) ENGINEERING PLANS |
| | |
| | A. THE ENGINEERING PLANS DO NOT SHOW THE CLEMATIS |
| | STREET PHASE III PROJECT RIGHT-OF-WAY IMPROVEMENTS. |
| | STAFF NEEDS TO VERIFY THAT THE PROPOSED FIBER CONDUIT, |
| | HANDHOLDS AND FUTURE COMMUNICATION POLES DO NOT |
| | INTERFERE WITH THE UNDER CONSTRUCTION RIGHT-OF-WAY |
| | PROJECT. |
| | |
| | B. TIE IN 2+43 IS SHOWN WITHIN A LANDSCAPE BULB OUT |
| | THAT IS BEING INSTALLED AS PART OF THE ADJACENT |
| | MIXED-USE DEVELOPMENT. THE BULB OUT IS SLATED TO HAVE A |
| | ROYAL PALM TREE INSTALLED WITHIN IT. IF THE PALM TREE |
| | HAS BEEN INSTALLED PRIOR TO THE BORE TAKING PLACE, THEN |
| | THE BORE MAY NOT UTILIZE THE LANDSCAPE AREA AND INSTEAD |
| | MUST BE STARTED MORE THAN 10 FEET FROM THE TREE, WHICH |
| | WOULD BE IN THE SIDEWALK. IF THE BORE IS DONE BEFORE |
| | THE TREE INSTALLATION IT MAY UTILIZE THE LANDSCAPE AREA |
| | AS THERE WILL BE NO TREE THAT COULD BE DAMAGED. |
| | |
| | C. THE ENGINEERING PLANS MUST INCLUDE THE NOTES STATING |
| | 1) UTILITIES MUST BE FIELD VERIFIED PRIOR TO DIGGING, |
| | 2) ALL CITY UTILITIES MUST BE LOCATED BY SOFT DIG |
| | METHODS BEFORE STARTING WORK, AND 3) TREE |
| | GRATE/PLANTING AREAS MAY NOT BE USED TO ASSIST IN THE |
| | BORE. THESE NOTES ARE ON OTHER ENGINEERING PLANS THAT |
| | HAVE BEEN SUBMITTED. |
| | |
| | D. THERE ARE MULTIPLE SHEETS MISSING FOR MERCER TO |
| | AUSTRALIAN (KEY INDICATES THESE AS THE 16 SERIES). THIS |
| | IS THE FIBER FOR SHEETS 6-8 OF THE SURVEY. NOTE: |
| | PROVIDED THE BORE REMAINS WITHIN THE RIGHT-OF-WAY AT 6 |
| | FEET DEEP, THERE SHOULD BE NO TREES IMPACTED. |
| | |
| | E. NO SURVEY WAS PROVIDED FOR SHEET 23 AND 24. THE |
| | ENGINEERING PLAN INCORRECTLY SHOWS THE OKEECHOBEE |
| | BOULEVARD RIGHT-OF-WAY. THE CITY OWNS UP TO THE BACK OF |
| | THE SIDEWALK, SO NO BORE OR HANDHOLE MAY OCCUR AS |
| | SHOWN. THIS APPLIES TO HANDHOLE 59+16 AND THE FIBER ON |
| | EITHER SIDE OF IT THAT IS UNDERNEATH THE LANDSCAPE |
| | AREA. |
| | |
| | F. TIE IN 78-16 DIRECTLY CONFLICTS WITH A LIGHT POLE |
| | AND MAY CONFLICT WITH THE FOOTERS OF THE BUILDING. |
| | |
| | G. THE BORE SHOWN AT 6 TO 12 FEET BELOW GRADE IS AT A |
| | SUFFICIENT DEPTH TO AVOID TREE AND PALM DAMAGE. |
| | |
| | PLEASE NOTE: |
| | |
| | THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811 |
| | TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL |
| | DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES MUST |
| | BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE |
| | WORK. |
| | |
| | THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A |
| | CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE |
| | WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES |
| | THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS, |
| | OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED. |
| | |