| 2022-12-30 09:59:20 | 1) SHEET 11, RELOCATE BORE AND BORE PIT SO IT IS NOT ON | | | TOP OF THE CITY'S 6" WM. | | | 2) SHEET 12, RELOCATE BORE AND BORE PIT SO IT IS NOT ON | | | TOP OF THE CITY'S 6" WM. | | | 3) SHEET 29, CITY HAS EXISTING 12" FM NOT SHOWN ON THE | | | PLANS | | | 4) SHEET 30, CITY HAS EXISTING 12" FM NOT SHOWN ON THE | | | PLANS | | | 5) REPEAT COMMENT: SHEET 26 TO 27, HIBISCUS NORTH TO | | | FERN, RELOCATE BORE TO WEST SIDE OF ROAD TO AVOID THE | | | CITY'S 24" STORM PIPE, 20" FORCE MAIN, AND 36" POTABLE | | | WATER MAIN | | | 6) SHEET 28, FERN STREET OPEN CUT, MILL AND RESURFACE | | | ON 50' EACH SIDE OF TRENCH REQUIRED INCLUDING | | | RESTRIPING WITH THE SPECIALTY BICYCLE MARKING PER CITY | | | DETAIL GC-9. | | | 7) GENERAL COMMENT, SIDEWALK RESTORATION REQUIRED PER | | | CITY STANDARD GC-1. ENTIRE FLAG OF SIDEWALK MUST BE | | | REPLACED. | | | SUZANNE BERGLUND | | | [email protected] |
|