| 2019-04-04 11:22:31 | PLUMBING 2ND REVIEW**DENIED** |
| | |
| | |
| | 1) THE FOLLOWING SHEETS HAVE THE P.E SIGNATURE AND SEAL |
| | AS COPIES.61G15-23.001 SHALL ACQUIRE A SEAL WITH WHICH |
| | SHE OR HE SHALL IDENTIFY ALL PLANS, SPECIFICATIONS OR |
| | REPORTS PREPARED OR ISSUED BY HER OR HIM AND FILED FOR |
| | PUBLIC RECORD. THE SEAL SHALL BE CAPABLE OF LEAVING A |
| | PERMANENT INK REPRESENTATION OR OTHER FORM OF EMBOSSING |
| | OR OPAQUE AND PERMANENT IMPRESSION, WHICH ALSO MAY BE |
| | COMPUTER GENERATED IMPRESSIONS, ON THE SURFACE OF |
| | PRINTS OR OTHER DUPLICATIONS OF DRAWINGS, AND, AS |
| | APPROPRIATE, UPON SPECIFICATION PAGES, AND OTHER |
| | ARTICLES OF SERVICE. WHERE REQUIRED, ELECTRONIC FILES |
| | MAY BE SEALED IN ACCORDANCE WITH RULE 61G15-23.001, |
| | F.A.C.SHT.A00,001,102,203,E200,M100,P100,101,200. |
| | PLEASE CORRECT AND RESUBMIT |
| | |
| | 2) SHT A-203 DETAIL #3 GRAB BAR TO BE MOUNTED @ 36" TO |
| | CENTER. GRAB BARS SHALL BE MOUNTED 33"-36" TO THE TOP |
| | GRIPPING SURFACE. FCB-A 609.4 |
| | |
| | 3) SHT. P-200 SHOW THE TOILET AS BEING DRY VENTED AND |
| | HAS THE DRINKING FOUNTAIN DISCHARGING INTO THE BATHROOM |
| | GROUP WET VENT. FBC 912.1 |
| | |
| | 4) THE DOOR SWING INTO THE CLEAR FLOOR SPACE OF THE LAV |
| | IS NOT PERMITTED UNLESS YOU COMPLY ALSO WITH FBC-A |
| | 305.3. FBC-A 603.2.3 |
| | |
| | 5) SHOW TOILET DISPENCER MEASURMENT FROM THE FRONT OF |
| | THE TOILET BOWL AS 7"-9". FBC-A 604.7 |
| | |
| | 6) P-101 DETAIL 5 PROVIDE NOTE THAT TEMPERING VALVE |
| | SHALL BE ASSE 1070. FBC-P 607.1.2 |
| | |
| | 7) LIST BACKFLOW AS REQUIRING A SEPERATE PERMIT. WPB |
| | ORD TO THE FBC 105.1 |
| | |
| | 8) PROVIDE SUPPORT DOCS SHOWING WATER HEATER SHELF WILL |
| | SUPORT THE WEIGHT OF THE WATER WITH IT FULL OF WATER. |
| | FBC 107.2.1 |
| | |
| | 9) SHT.A-203 PROVIDE MEASUREMENT SHOW THE GRAB BAR IS |
| | TO BE MOUNTED 12" FROM THE CENTER LINE OF THE TOILET. |
| | FBC-A 604.5.2 |
| | |
| | 10) SHT A-203 SHOW DIMENSIONS FOR SIDE GRAB BAR AS |
| | 42"MIN LONG, AND THE OVERALL @54" FROM BACKWALL. FBC-A |
| | 604.5.1 |
| | |
| | |
| | |