| Plan Review Notes For Permit 19020050 |
| Permit Number |
19020050 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-04 14:21:08 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) ENSURE THAT THERE IS FIRE SPRINKLER ALARM DEVICE IS | | | INSTALLED IN THIS SUITE. THE DEVICE IS TO TIED INTO THE | | | ENTIRE BUILDING FIRE SPRINKLER ALARM. | | | | | | | | | PER NFPA 101, CHAPTER 37, EXISTING MERCANTILE | | | OCCUPANCIES | | | | | | 37.4.5.4.3 OCCUPANT NOTIFICATION. DURING ALL TIMES THAT | | | THE MERCANTILE | | | OCCUPANCY IS OCCUPIED, THE REQUIRED FIRE ALARM SYSTEM, | | | ONCE INITIATED, | | | SHALL PERFORM ONE OF THE FOLLOWING FUNCTIONS: | | | (1) IT SHALL ACTIVATE AN ALARM IN ACCORDANCE WITH 9.6.3 | | | THROUGHOUT THE | | | MERCANTILE OCCUPANCY, AND POSITIVE ALARM SEQUENCE IN | | | ACCORDANCE | | | WITH 9.6.3.4 SHALL BE PERMITTED. | | | (2) OCCUPANT NOTIFICATION SHALL BE PERMITTED TO BE MADE | | | VIA A VOICE | | | COMMUNICATION OR PUBLIC ADDRESS SYSTEM IN ACCORDANCE | | | WITH | | | 9.6.3.9.2. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|