Plan Review Notes
Plan Review Notes For Permit 19020050
Permit Number 19020050
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-02-04 14:21:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) ENSURE THAT THERE IS FIRE SPRINKLER ALARM DEVICE IS
 INSTALLED IN THIS SUITE. THE DEVICE IS TO TIED INTO THE
 ENTIRE BUILDING FIRE SPRINKLER ALARM.
  
  
 PER NFPA 101, CHAPTER 37, EXISTING MERCANTILE
 OCCUPANCIES
  
 37.4.5.4.3 OCCUPANT NOTIFICATION. DURING ALL TIMES THAT
 THE MERCANTILE
 OCCUPANCY IS OCCUPIED, THE REQUIRED FIRE ALARM SYSTEM,
 ONCE INITIATED,
 SHALL PERFORM ONE OF THE FOLLOWING FUNCTIONS:
 (1) IT SHALL ACTIVATE AN ALARM IN ACCORDANCE WITH 9.6.3
 THROUGHOUT THE
 MERCANTILE OCCUPANCY, AND POSITIVE ALARM SEQUENCE IN
 ACCORDANCE
 WITH 9.6.3.4 SHALL BE PERMITTED.
 (2) OCCUPANT NOTIFICATION SHALL BE PERMITTED TO BE MADE
 VIA A VOICE
 COMMUNICATION OR PUBLIC ADDRESS SYSTEM IN ACCORDANCE
 WITH
 9.6.3.9.2.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  