| 2019-02-13 09:17:14 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020050 |
| | ADD: 801 VILLAGE BLVD., SUITE: 305 |
| | CONT: BLUE DOLPHIN CONSTRUCTION LLC |
| | TEL: 786-205-1242 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 13/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A102 INDICATES THE TRAVEL DISTANCE FROM THE |
| | FRONT OF THE SUITE TO THE REAR IS OVER 75 FEET, AN |
| | OCCUPANT LOAD OF 45 FIRE SPRINKLERED FOR A MERCANTILE/ |
| | BUSINESS OCCUPANCY THE 2017 FBC-B TABLE 1006.2.1 COMMON |
| | PATH OF TRAVEL IS LIMITED TO 75 FEET WHICH WILL REQUIRE |
| | TWO EXITS. PLEASE SHOW COMPLIANCE WITH: |
| | |
| | 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF |
| | EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 2) IF THE REAR EXIT IS NOT ACCESSIBLE, THEN SHOW HOW UP |
| | TO $5,000.00 DOLLARS COULD BE SPENT ON ACCESSIBLE |
| | UPGRADES, SEE THE ORDER IN WHICH THE FUNDS ARE TO BE |
| | SPENT. |
| | 2017 ACCESSIBILITY CODE SECTION 202.4.1DISPROPORTIONATE |
| | COST. ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | EITHER THE DESIGN PROFESSIONAL OR CONTRACTOR ON THEIR |
| | LETTERHEAD NEEDS TO SHOW AN ITEMIZED DOLLAR AMOUNT FOR |
| | ACCESSIBLE UPGRADES TO REACH EITHER CODE COMPLIANCE OR |
| | THE DISPROPORTIONATE COST OF $5,000.00 IN VALUE. |
| | |
| | 3) PLEASE NOTE SHEET A001 THE LIFE SAFETY PLAN NOR A102 |
| | DO NOT SHOW DETAILS FOR NEITHER THE BREAK ROOM SINK OR |
| | THE RESTROOM. SHEET A102 DOES SHOW A DETAIL 1/A203 FOR |
| | THE RESTROOM, BUT THERE IS NO SUCH SHEET LISTED IN THE |
| | SHEET INDEX NOR IS THERE SUCH SHEET IN THE SET OF |
| | PLANS. CODE COMPLIANCE FOR THESE ELEMENTS CANNOT BE |
| | REVIEWED FOR THIS REVIEW. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. THE ACCESSIBILITY REQUIREMENTS |
| | FOUND IN CHAPTER 6 OF THE ACCESSIBILITY CODE CANNOT BE |
| | REVIEWED. |
| | |
| | 4) THE M101 & M200 SHOW A MAKE-UP AIR WALL LOUVER |
| | REQUIRED, PLEAS PROVIDE THE PRODUCT APPROVAL FOR THIS |
| | PRODUCT. PLEASE COMPLY WITH: / 2017 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31? WALL LOUVERS |
| | |
| | 5) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE WALL |
| | LOUVER, NOT FOUND ON EITHER THE ARCHITECTURAL OR |
| | MECHANICAL SHEETS. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 6.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 6.2. RISK CATEGORY. |
| | |
| | 6.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 6.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 6.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |