| 2019-07-03 14:22:51 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020046 |
| | 7/3/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | KAMM COUNSULTING THE MECHANICAL ENGINEERS OF RECORD |
| | WERE NOTIFIED ON TUESDAY- 7/2/19 THAT THE PLANS HAD |
| | FAILED FOR THE DEFIENCIES LISTED BELOW. |
| | |
| | 1) SHEET M2.1: THE CORRECTED PLAN SHOWS THE RELOCATED |
| | 8" O/A DUCT PENETRATING THE INTERIOR EXIT STAIRWAY #115 |
| | WHICH IS PROHIBITED PER SECTION 1023.5 & 1023.6 FBC B. |
| | |
| | 2) M2.1: THE REQUESTED OUTSIDE AIR DAMPERS FOR AHU'S |
| | 1A, 1B, 3A AND 2C ARE THE MANUALLY CONTROLLED TYPE, |
| | HOWEVER THE DAMPERS ARE REQUIRED TO FUNCTION |
| | AUTOMATICALLY PER SECTION C403. 2.4.3 FBC EC. |
| | |
| | 3) M2.1: THE RELOCATED O/A INLET TO THE WEST SIDE OF |
| | THE BUILDING IS WITHIN 10' OF THE PARKING LOT WHICH IS |
| | PROHIBITED PER SECTION 401.4 (2) FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |