Plan Review Notes
Plan Review Notes For Permit 19020046
Permit Number 19020046
Review Stop M
Sequence Number 3
Notes
Date Text
2019-07-03 14:22:513RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19020046
 7/3/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 KAMM COUNSULTING THE MECHANICAL ENGINEERS OF RECORD
 WERE NOTIFIED ON TUESDAY- 7/2/19 THAT THE PLANS HAD
 FAILED FOR THE DEFIENCIES LISTED BELOW.
  
 1) SHEET M2.1: THE CORRECTED PLAN SHOWS THE RELOCATED
 8" O/A DUCT PENETRATING THE INTERIOR EXIT STAIRWAY #115
 WHICH IS PROHIBITED PER SECTION 1023.5 & 1023.6 FBC B.
  
 2) M2.1: THE REQUESTED OUTSIDE AIR DAMPERS FOR AHU'S
 1A, 1B, 3A AND 2C ARE THE MANUALLY CONTROLLED TYPE,
 HOWEVER THE DAMPERS ARE REQUIRED TO FUNCTION
 AUTOMATICALLY PER SECTION C403. 2.4.3 FBC EC.
  
 3) M2.1: THE RELOCATED O/A INLET TO THE WEST SIDE OF
 THE BUILDING IS WITHIN 10' OF THE PARKING LOT WHICH IS
 PROHIBITED PER SECTION 401.4 (2) FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  