Plan Review Notes
Plan Review Notes For Permit 19020046
Permit Number 19020046
Review Stop B
Sequence Number 3
Notes
Date Text
2019-07-02 16:53:12PLAN REVIEW COMMENTS
  
 3RD REVIEW:
 FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) DEFERRED.
  
 4) TO BE ADDRESSED. THE PLANS INDICATE THAT HABITABLE
 SPACE IS BEING ADDED TO THE BUILDING. THIS WILL REQUIRE
 AN IMPACT FEE REVIEW BY PALM BEACH COUNTY. IMPACT FEES
 - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 5) NOT COMPLIED. (3RD REVIEW REQUEST) THE EXIT
 SEPARATION DISTANCES ON THE LIFE SAFETY PLANS ARE USING
 ONE-THIRD THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE AREA SERVED RATHER THAN ONE-HALF AS
 REQUIRED BY FBC 1007.1.1. EXCEPTION NUMBER 2 ALLOWS
 ONE-THIRD WHEN THE BUILDING IS SPRINKLERED THROUGHOUT
 WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM. THIS
 BUILDING IS NOT SPRINKLERED. THE TWO EXITS FROM THE
 ASSEMBLY AREA ARE SEPARATED BY 36 FEET, HOWEVER, THE
 CORRIDORS THAT THEY DISCHARGE INTO (NUMBERS 103 AND
 113) ARE NOT PHYSICALLY SEPARATED FROM EACH OTHER BY
 FIRE RATED WALLS OR DOORS AND ARE LESS THAN 25 FEET
 APART AT ONE POINT. THEY ARE TECHNICALLY SHARING THE
 SAME CORRIDOR. THE CODE REQUIREMENTS TABLE ON SHEET
 A0.02 STATES THAT 4 EXITS ARE PROVIDED. THERE ARE ONLY
 3 EXITS PER THE PLANS. THE COMMON PATH OF TRAVEL IN THE
 TABLE IS 100', HOWEVER, IT IS 75' FOR ASSEMBLY
 OCCUPANCIES PER FBC TABLE 1006.1. THESE ITEMS STILL
 NEED TO BE ADDRESSED. 5A)FBC 1020.1 AND TABLE 1020.1
 REQUIRES CORRIDORS SERVING OCCUPANT LOADS GREATER THAN
 30 IN BUILDINGS WITHOUT SPRINKLER SYSTEMS TO HAVE A
 FIRE-RESISTANCE RATING OF 1 HOUR FOR ASSEMBLY AND
 BUSINESS OCCUPANCIES. 5B) SHOW THAT THE SEPARATION
 DISTANCE OF THE REQUIRED EXITS FROM THE BOARD ROOM AND
 THE BUILDING COMPLY WITH FBC 1007.1.1. THE EXITS ARE
 REQUIRED TO BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN ONE-HALF OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED
 MEASURED IN A STRAIGHT LINE BETWEEN THEM. 5C) SHOW THE
 COMMON PATH OF TRAVEL DISTANCES ON THE PLANS. PROVIDE A
 MORE DETAILED LIFE SAFETY PLAN, FBC 107.2.1. CLEARLY
 IDENTIFY ALL EXITS, FBC 1006. SHOW ALL REQUIRED MEANS
 OF EGRESS PATHS OF TRAVEL, FBC 1005. SPECIFY THE DOOR
 WIDTHS AND THE NUMBER OF OCCUPANTS THAT WILL BE USING
 EACH EXIT, FBC 1005. SHOW THE EXIT/EXIT ACCESS
 SEPARATION DISTANCE REQUIRED BY FBC 1007.1.1
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) DEFERRED.
  
 11) DEFERRED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15) WILL COMPLY. THE STRUCTURAL PLANS SHOW A NEW
 FOOTING FOR THE NEW EXTERIOR WALL. THERE WAS NO SURVEY
 SUBMITTED TO SHOW THE LOCATION OF THE EXTERIOR WALL
 WITH RELATION TO THE PROPERTY LINE. IT IS NOT CLEAR ON
 THE STRUCTURAL DRAWING IF THE PROPERTY LINE DRAWN IS AN
 ACCURATE REPRESENTATION. THE NEW FOOTING FOR THE
 EXTERIOR WALL CAN NOT EXTEND BEYOND THE PROPERTY LINE.
 FBC 107.2.5
  
 16) NOT COMPLIED. THE PROFESSIONAL ENGINEER'S DIGITAL
 SIGNATURE ON THE ENERGY FORMS IS SELF CERTIFIED. THE
 BOARD OF PROFESSIONAL ENGINEERS HAS ADVISED THAT AN
 ENGINEER'S DIGITAL SIGNATURE REQUIRES A THIRD PARTY
 CERTIFICATION. NEW COMMENT. THE COST OF THIS PROJECT IS
 MORE THAN 30 PERCENT OF THE ASSESSED VALUE OF THE
 STRUCTURE. THEREFORE THIS IS CONSIDERED A RENOVATED
 BUILDING AND IS REQUIRED TO COMPLY WITH THE 2017 FBC
 ENERGY CONSERVATION. SUBMIT THE REQUIRED CONSTRUCTION
 DOCUMENTS TO SHOW THAT THE PROJECT COMPLIES WITH THE
 FBC ENERGY CONSERVATION. SEE SECTION C103.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  