2019-05-06 10:35:422ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19020046
 5/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2.1 & M6.1: THE REQUESTED OUTSIDE AIR
 DAMPERS WERE NOT PROVIDED FOR AHU'S 1A, 1B, 3A AND 2C-
 SECTION C403. 2.4.3 FBC EC. AHU- 2C IN THE CORRIDOR
 DOES NOT HAVE AN O/A DUCT, HOWEVER O/A IS REQUIRED ROR
 THE CORRIDOR- TABLE 403.3.1.1 FBC M.
  
 2) M2.1: NO MAKEUP AIR HAS BEEN PROVIDED FOR THE TOILET
 ROOM EXHAUST SYSTEMS- SECTION 501.4 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  