| Plan Review Notes For Permit 19020046 |
| Permit Number |
19020046 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-05-06 10:35:42 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #19020046 | | | 5/6/19 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS M2.1 & M6.1: THE REQUESTED OUTSIDE AIR | | | DAMPERS WERE NOT PROVIDED FOR AHU'S 1A, 1B, 3A AND 2C- | | | SECTION C403. 2.4.3 FBC EC. AHU- 2C IN THE CORRIDOR | | | DOES NOT HAVE AN O/A DUCT, HOWEVER O/A IS REQUIRED ROR | | | THE CORRIDOR- TABLE 403.3.1.1 FBC M. | | | | | | 2) M2.1: NO MAKEUP AIR HAS BEEN PROVIDED FOR THE TOILET | | | ROOM EXHAUST SYSTEMS- SECTION 501.4 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|