Plan Review Notes
Plan Review Notes For Permit 19020046
Permit Number 19020046
Review Stop B
Sequence Number 2
Notes
Date Text
2019-05-21 19:13:43PLAN REVIEW COMMENTS
  
 2ND REVIEW:
 FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOTED. ASBESTOS: IN ACCORDANCE WITH SECTION 553.79
 F. S. THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS'
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 2) COMPLIED. THIS PROJECT IS AN ALTERATION AND ADDITION
 TO AN EXISTING BUILDING. THIS IS A LEVEL 3 ALTERATION
 BECAUSE THE WORK AREA IS THE ENTIRE BUILDING. SPECIFY
 THE LEVEL OF ALTERATION ON THE PLANS. FBC 107.2.1 & FBC
 EXISTING BUILDING 505
  
 3) REQUEST TO DEFER. PROVIDE ADDITIONAL INFORMATION ON
 THE ACCESSIBLE LIFT THAT IS PROPOSED TO PROVIDE
 VERTICAL ACCESS TO THE SECOND FLOOR. PLEASE CLARIFY IF
 THIS IS A LIFT OR AN ELEVATOR. PROVIDE CONSTRUCTION
 DETAILS AND DIMENSIONS FOR THE LIFT'S SHAFT/ELEVATOR
 HOISTWAY. SPECIFY THE DIMENSIONS OF THE LIFT/ELEVATOR
 CAR. PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 LIFT/ELEVATOR. FBC 107.2.1, FBC CHAPTER 30 & FBC
 ACCESSIBILITY 407.
  
 4) TO BE ADDRESSED. THE PLANS INDICATE THAT HABITABLE
 SPACE IS BEING ADDED TO THE BUILDING. THIS WILL REQUIRE
 AN IMPACT FEE REVIEW BY PALM BEACH COUNTY. IMPACT FEES
 - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 5) NOT COMPLIED. THESE ITEMS STILL NEED TO BE
 ADDRESSED. 5A)FBC 1020.1 AND TABLE 1020.1 REQUIRES
 CORRIDORS SERVING OCCUPANT LOADS GREATER THAN 30 IN
 BUILDINGS WITHOUT SPRINKLER SYSTEMS TO HAVE A
 FIRE-RESISTANCE RATING OF 1 HOUR FOR ASSEMBLY AND
 BUSINESS OCCUPANCIES. 5B) SHOW THAT THE SEPARATION
 DISTANCE OF THE REQUIRED EXITS FROM THE BOARD ROOM AND
 THE BUILDING COMPLY WITH FBC 1007.1.1. THE EXITS ARE
 REQUIRED TO BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN ONE-HALF OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE BUILDING OR AREA TO BE SERVED
 MEASURED IN A STRAIGHT LINE BETWEEN THEM. 5C) SHOW THE
 COMMON PATH OF TRAVEL DISTANCES ON THE PLANS. PROVIDE A
 MORE DETAILED LIFE SAFETY PLAN, FBC 107.2.1. CLEARLY
 IDENTIFY ALL EXITS, FBC 1006. SHOW ALL REQUIRED MEANS
 OF EGRESS PATHS OF TRAVEL, FBC 1005. SPECIFY THE DOOR
 WIDTHS AND THE NUMBER OF OCCUPANTS THAT WILL BE USING
 EACH EXIT, FBC 1005. SHOW THE EXIT/EXIT ACCESS
 SEPARATION DISTANCE REQUIRED BY FBC 1007.1.1
  
 6) COMPLIED. THE DOOR ON GROUND LEVEL AT THE NORTHWEST
 CORNER OF THE BUILDING IN CORRIDOR #125 CAN NOT BE USED
 AS AN EXIT. THE EXIT DISCHARGES ONTO THE ADJACENT
 PROPERTY AND DOES NOT OPEN TO A PUBLIC WAY AS REQUIRED.
 FBC 1022.2.2
  
 7) COMPLIED, THIS AREA IS NOT A KITCHEN. THE LIFE
 SAFETY PLAN APPEARS TO SHOW AN EXIT EGRESS THROUGH A
 KITCHEN AREA (CAFE, ROOM #114). FBC 1016.2 (5) DOES NOT
 ALLOW EGRESS TO PASS THROUGH KITCHENS.
  
 8) TO BE ADDRESSED. THE BUILDING OFFICIAL HAS AGREED TO
 ACCEPT THE DESIGN OCCUPANT LOAD OF 165 PERSONS USING
 THE 15 NET LOAD FACTOR, AS LONG AS, A SIGN IS POSTED
 CONSPICUOUSLY NEAR THE MAIN ENTRANCE TO THE BOARD ROOM
 THAT STATES THE MAXIMUM OCCUPANCY FOR THE ROOM IS 165
 PERSONS. THIS NEEDS TO BE SPECIFIED ON THE PLANS. SEE
 FBC1004.3. PLEASE EXPLAIN HOW THE OCCUPANT LOAD FACTOR
 OF 15 NET WAS DETERMINED FOR THE ASSEMBLY AREA. THE
 PLANS APPEAR TO SHOW CONCENTRATED CHAIRS THAT ARE NOT
 FIXED, WHICH WOULD BE AN OCCUPANT LOAD FACTOR OF 7 NET.
 IF THE CHAIRS ARE NOT PRESENT, THIS COULD BE CONSIDERED
 STANDING SPACE WITH AN OCCUPANT LOAD FACTOR OF 5 NET.
 FBC TABLE 1004.1.2
  
 9) TO BE ADDRESSED. THE SPECIFIC ITEMS THAT YOU WISH TO
 BE DEFERRED ARE REQUIRED TO BE LISTED ON THE PLANS.NO
 PRODUCT APPROVALS HAVE BEEN SUBMITTED FOR THE EXTERIOR
 DOORS, WINDOWS AND STOREFRONTS AS REQUIRED BY FBC
 107.3.4 & FS 553.842 (5). 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10) TO BE ADDRESSED WHEN DEFERRED ITEMS ARE SUBMITTED.
 IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURE'S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) TO BE ADDRESSED WHEN DEFERRED ITEMS ARE SUBMITTED.
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 12) NOT ADDRESSED. THE SPECIFIC ITEMS THAT YOU WISH TO
 BE DEFERRED ARE TO BE LISTED ON THE PLANS. 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 13) COMPLIED. THRESHOLDS ACCESS. CODE 404.2.5.
 THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH
 (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN
 LEVEL AT DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 14) NOT COMPLIED. THIS IS TO BE NOTED ON THE PLANS. THE
 STRUCTURAL DRAWINGS INDICATE THAT THE METAL BAR JOISTS
 WILL BE MODIFIED. THE FOLLOWING WILL APPLY.
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 15) WILL COMPLY. THE STRUCTURAL PLANS SHOW A NEW
 FOOTING FOR THE NEW EXTERIOR WALL. THERE WAS NO SURVEY
 SUBMITTED TO SHOW THE LOCATION OF THE EXTERIOR WALL
 WITH RELATION TO THE PROPERTY LINE. IT IS NOT CLEAR ON
 THE STRUCTURAL DRAWING IF THE PROPERTY LINE DRAWN IS AN
 ACCURATE REPRESENTATION. THE NEW FOOTING FOR THE
 EXTERIOR WALL CAN NOT EXTEND BEYOND THE PROPERTY LINE.
 FBC 107.2.5
  
 16) NEW COMMENT. THE COST OF THIS PROJECT IS MORE THAN
 30 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
 THEREFORE THIS IS CONSIDERED A RENOVATED BUILDING AND
 IS REQUIRED TO COMPLY WITH THE 2017 FBC ENERGY
 CONSERVATION. SUBMIT THE REQUIRED CONSTRUCTION
 DOCUMENTS TO SHOW THAT THE PROJECT COMPLIES WITH THE
 FBC ENERGY CONSERVATION. SEE SECTION C103.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  