| Plan Review Notes For Permit 19020046 |
| Permit Number |
19020046 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-25 13:57:56 | PLAN DENIED | | | 1) PROVIDE DUCT SIZE FOR RETURN AIR. PER SECTION | | | 107 FBC 2017. | | | 2) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS | | | FOR OUTDOOR AIR. 2017 FLORIDA ENERGY CODE. | | | 3) REFER TO TABLE 1502.2.3 ROOF MOUNTED EQUIPMENT | | | HIGHT REQUIREMENTS 2017 FBC | | | 4) REFER TO SECTION 604.8 LINING INSTALLATION | | | 2017 FBC (M) (LINED ROUND METAL DUCT ONLY ) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|