| 2019-04-11 15:00:42 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020031 |
| | 4/11/19 |
| | |
| | COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT |
| | ADDRESSED- NO CORRECTIONS WERE MADE TO THE PLANS AND NO |
| | RESPONSE NARRATIVE ADDRESSING THE COMMENTS WAS |
| | SUBMITTED. |
| | |
| | PLEASE REVIEW THE COMMENTS LISTED BELOW AND COMPLY. |
| | |
| | |
| | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020031 |
| | 3/1/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M100: PLEASE PROVIDE A SCOPE OF WORK OUTLINE |
| | ON THE PLAN- SECTION 107.2.1 WPB. |
| | |
| | 2) M100: BASED ON THE ARCHITECTURAL PLANS, THE PROPOSED |
| | PROJECT APPEARS TO BE A CHANGE OF OCCUPANCY, OR A LEVEL |
| | III ALTERATION AS INDICATED ON LS100. REFER TO SECTION |
| | 809.2 FBC-17 EXISTING BUILDING CODE AND PROVIDE MINIMUM |
| | VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER |
| | TABLE 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE |
| | THAT INDICATES THE REQUIRED AND PROVIDED CFMS OF |
| | OUTDOOR AIR. |
| | |
| | 3) M100: THE PLAN APPEARS TO SHOW A NEW 5-TON AC SYSTEM |
| | WITH THE AIR HANDLER BEING INSTALLED IN THE ATTIC. |
| | PLEASE SEE SECTION C403.2.9.6 FBC EC WHICH PROHIBITS |
| | INSTALLATION OF AIR HANDLERS IN ATTICS. |
| | |
| | 3) M100: A DUCT SMOKE DETECTORS IS REQUIRED IN THE |
| | SUPPLY AIR SYSTEMS OF THE NEW 5-TON AC SYSTEM PER |
| | SECTION 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE |
| | APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE |
| | THE SYSTEM IS NOT CAPABLE OF PRODUCING OVER 2000 CFMS |
| | OF SUPPLY AIR. |
| | |
| | 4) M100: PROVIDE THE DIMENSIONS OF THE RETURN GRILLS IN |
| | THE OFFICES- SECTION 603 FBC M. |
| | |
| | 5) M100: PROVIDE AIR DEVICE AND AIR DISTRIBUTION |
| | SCHEDULES THAT INDICATE THE MAKES AND MODELS OF THE |
| | DIFFUSERS AND GRILLS, AND TYPE OF DUCTWORK TO BE |
| | INSTALLED- SECTION 603. |
| | |
| | 6) M100: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FLOOR GRILLS IN COMPLIANCE WITH SECTION 603.18.1 FBC M. |
| | THE SPECS MUST INDICATE THE GRILLS SHALL RESIST |
| | STRUCTURAL FAILURE AS OUTLINED IN THE SECTION. |
| | |
| | 7) M100: PROVIDE A BATH AND TOILET ROOM EXHAUST FAN |
| | SCHEDULE, AND SHOW THE EXHAUST DUCT RUNS AND |
| | TERMINATION LOCATIONS- TABLE 403.3.1.1 FBC M. |
| | |
| | 8) M100: PROVIDE EQUIPMENT SCHEDULES AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS FOR ANY COOKING |
| | APPLIANCES TO BE INSTALLED IN THE KITCHEN AND BAR- |
| | SECTION 917 FBC M. PLEASE IDENTIFY THE LOCATIONS OF THE |
| | APPLIANCES ON THE PLAN AND PRPOVIDE LOCAL EXHAUST |
| | SYSTEMS (HOODS) WHERE REQUIRED. PLEASE NOTE THAT |
| | SEPARATE PERMITS ARE REUIRED FOR GREASE EXHAUST |
| | SYSTEMS- SECTION 107.2.1 WPB. |
| | |
| | 9) M100: EXHAUST VENTILATION IS REQUIRED FOR THE |
| | KITCHEN AT A RATE OF 25 CFMS CONTINUOUSLY OR 100 CFMS |
| | INTERMITTENTLY IN ACCORDANCE WITH TABLE 403.3.1.1 FBC |
| | M. PLEASE NOTE FOOTNOTE B PROHIBITS RECIRCULATION OF |
| | AIR FROM THE KITCHEN TO OTHER OCCUPIED ROOMS AND |
| | SPACES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |