| Plan Review Notes For Permit 19020031 |
| Permit Number |
19020031 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-02 16:58:57 | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 | | | | | | NOTHING IN A COMMERCIAL CALCULATION HAS 10,000 AT 100% | | | AND REMAINDER AT 40% THAT IS A RESIDENTIAL CALCULATION |
|