| 2019-04-20 13:36:51 | ***CORRECTIONS*** |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 2ND REVIEW DENIED: |
| | |
| | 1. WORK COMPLETED WITHOUT THE BENEFIT OF PERMITS. THE |
| | SHEET A100 SHOWS THE FRONT ENTRY SET OF DOORS AS A PAIR |
| | OF INSWING DOORS. THE CHANGE OF OCCUPANCY PERMIT |
| | 10070543 SHOWS THESE DOORS AS OUTSWING DOORS. THERE WAS |
| | ALSO A MISC. PERMIT FILED UNDER THE ADDRESS OF 339 |
| | WESTMINSTER PL. PERMIT NUMBER 08040046, NOA 07?0522.05 |
| | HARMAN WINDOWS AND DOORS FOR OUTSWING GLAZED WOOD |
| | FRENCH DOORS, L. M. IMPACT TESTED. PLEASE PROVIDE THE |
| | PRODUCT TESTING FOR THESE DOORS FOR INSWING USE. |
| | FAIL: (AS PER N.O.A. # 07-0522.05, THE ENTRY DOORS MUST |
| | BE SHOWN ON THE PLANS WITH AN OUTSWING) |
| | |
| | 2. OK (2017 FBC B TYPE VB ACKNOWLEDGED BY DESIGN |
| | PROFESSIONAL) |
| | 3. OK (ACKNOWLEDGED BY DESIGN PROFESSIONAL) |
| | 4. OK (ACKNOWLEDGED BY DESIGN PROFESSIONAL) |
| | 5.A. OK (LEVEL III IDENTIFIED ON PLANS/ACKNOWLEDGED BY |
| | DESIGN PROFESSIONAL) |
| | 5.B. OK (ACKNOWLEDGED BY DESIGN PROFESSIONAL) |
| | 6.A., B., & C. |
| | FAIL: (ALL PRODUCT APPROVALS FOR GLAZING, WINDOWS, |
| | DOORS, MULLIONS, WALL LOUVERS, ROOFING PRODUCTS & |
| | ASSEMBLIES NEED TO BE REVIEW STAMPED/SIGNED BY DESIGN |
| | PROFESSIONAL & SUBMITTED TO THE CITY FOR APPROVAL) |
| | |
| | 6.D. OK (ACKNOWLEDGED BY DESIGN PROFESSIONAL) |
| | 7. SHEET A?101 THE FLOOR PLAN AND SHEET A?500 THE DOOR |
| | SCHEDULE WILL NEED TO MEET THE REQUIREMENT OF THE 2017 |
| | FBC?B SECTION 1010.1.1 SIZE OF DOORS. THE REQUIRED |
| | CAPACITY OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR |
| | THE OCCUPANT LOAD THEREOF AND SHALL PROVIDE A MINIMUM |
| | CLEAR WIDTH OF 32 INCHES. CLEAR OPENINGS OF DOORWAYS |
| | WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE |
| | OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| | DEGREES. THE DOORS IDENTIFIED AS 102, 108 & 110 DO NOT |
| | MEET THIS REQUIREMENT. |
| | FAIL: (IT APPEARS THAT THE SIZE OF DOOR 102 HAS NOT |
| | BEEN ADJUSTED ON THE DOOR SCHEDULE) |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |