| 2019-04-01 10:41:59 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) JOB VALUE SEEMS LOW: PROVIDE ACTUAL COST SO AS TO |
| | COMPLY WITH 109.3 BUILDING PERMIT VALUATIONS. IF, IN |
| | THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| | VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| | SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2) WASHING MACHINE IS MISSING FROM THE SANITARY RISER |
| | DRAWING. TOILET ARE SHOW AS 2" AND THE TUB IS NOT |
| | PERMITTED TO BE VENTED BY THE KITCHEN SINK. THE FITTING |
| | MUST BE IN DIRECTION OF FLOW. PLEASE PROVIDE A CODE |
| | COMPLIANT ISOMETRIC. FBC 107.3.5 |
| | |
| | 3) PROVIDE MANUFACTURES INSTALLATION MAUNAL SHOWING THE |
| | NEW WATER HEATER WITH MEET THE D.O.E ENERGY MIN OF .92 |
| | U.E.F |
| | |
| | 4) PROVIDE FLOW RATED, PRESSURE AND G.P.M SHOWING HOW |
| | YOUR COMPLYING WITH FBC-R P 2903.1 BEING ALL OF YOUR |
| | WATER PIPING IS 1/2" |
| | |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |