| Plan Review Notes For Permit 19020018 |
| Permit Number |
19020018 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-15 13:42:49 | PROVISO: | | | | | | COMPLIANCE WITH NOTIFICATION COVERAGE SUBJECT TO FIELD | | | INSPECTION. | | | | | | 7.8.1.2.2 (NFPA 101) AUTOMATIC, MOTION SENSOR-TYPE | | | LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS | | | OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE | | | EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION | | | TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND | | | THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT | | | IN THE AREA SERVED BY THE LIGHTING UNITS. | | | | | | 7.2.1.6.2 #6 (NFPA 101) THE ACTIVATION OF MANUAL FIRE | | | ALARM BOXES THAT ACTIVATE THE BUILDING FIRE - | | | PROTECTIVE SIGNALING SYSSPECIFIED IN 7.2.1.6.2 (6) | | | SHALL BE REQUIRED TO UNLOCK THE DOORS. | | | | | | S. THOMAS | | | 561-804-4728 |
|