Plan Review Notes
Plan Review Notes For Permit 19011386
Permit Number 19011386
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-23 07:34:211) INDICATE ON BOTH SETS OF PLANS THE TYPE OF FLOORING
 THAT IS BEING INSTALLED. THE PERMIT APPLICATION STATES"
 NEW FLOORING."WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 2) TWO DIFFERENT DOCUMENTS HAVE BEEN SUBMITTED FOR
 FLOORING UNDERLAYMENT.ONE IS FOR "FLOORMUFFLER" AND THE
 OTHER IS FOR "SENTINEL". WHICH PRODUCT IS PLANNED ON
 BEING USED? CLARIFY. WPB AMEND. TO FBC SEC.
 107.2.1.REMOVE ANY OLD DOCUMENTS FROM THE PERMIT
 PACKAGE THAT DO NOT APPLY.2ND REQUEST.
 4) THE FLOOR UNDRELAYMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF THE 2017 FBC SEC. 1207.2 FOR AIR-BORNE
 SOUND FOR THE TYPE OF FLOORING MATERIAL BEING
 INSTALLED. 2ND REQUEST.
 5) THE FLOOR UNDERLAYMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF 2017 FBC SEC.1207.3 FOR STRUCTURE-BORNE
 SOUND FOR THE TYPE OF FLOORING MATERIAL BEING
 INSTALLED. 2ND REQUEST.
 6) SUBMIT TWO COPIES OF THE NONCOMBUSTIBILITY TEST FOR
 THE UNDERLAYMENT AS REQUIRED BY 2017 FBC SECS.703.5.1
 AND 703.5.2. 2ND REQUEST.
 7) SHOW THE WALL AREAS ON THE PLANS WHERE THE DRYWALL
 WILL BE REPLACED. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  