2019-02-13 11:24:441) SUBMIT TWO COPIES OF THE FLOOR PLANS FOR THE WORK TO
 BE DONE. ONLY ONE COPY WAS IN THE APPLICATION
 PACKAGE.WPB AMEND. TO FBC SEC. 107.1, 107.2.1.
 2) INDICATE ON BOTH SETS OF PLANS THE TYPE OF FLOORING
 THAT IS BEING INSTALLED. THE PERMIT APPLICATION STATES"
 NEW FLOORING."WPB AMEND. TO FBC SEC. 107.2.1.
 3) TWO DIFFERENT DOCUMENTS HAVE BEEN SUBMITTED FOR
 FLOORING UNDERLAYMENT.ONE IS FOR "FLOORMUFFLER" AND THE
 OTHER IS FOR "SENTINEL". WHICH PRODUCT IS PLANNED ON
 BEING USED? CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE FLOOR UNDRELAYMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF THE 2017 FBC SEC. 1207.2 FOR AIR-BORNE
 SOUND FOR THE TYPE OF FLOORING MATERIAL BEING
 INSTALLED.
 5) THE FLOOR UNDERLAYMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF 2017 FBC SEC.1207.3 FOR STRUCTURE-BORNE
 SOUND FOR THE TYPE OF FLOORING MATERIAL BEING
 INSTALLED.
 6) SUBMIT TWO COPIES OF THE NONCOMBUSTIBILITY TEST FOR
 THE UNDERLAYMENT AS REQUIRED BY 2017 FBC SECS.703.5.1
 AND 703.5.2.
 7) SHOW THE WALL AREAS ON THE PLANS WHERE THE DRYWALL
 WILL BE REPLACED AND SHOW THE TYPE OF BACKER BOARD THAT
 WILL BE INSTALLED IN THE SHOWER AREA.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  