| Plan Review Notes For Permit 19011386 |
| Permit Number |
19011386 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-13 11:24:44 | 1) SUBMIT TWO COPIES OF THE FLOOR PLANS FOR THE WORK TO | | | BE DONE. ONLY ONE COPY WAS IN THE APPLICATION | | | PACKAGE.WPB AMEND. TO FBC SEC. 107.1, 107.2.1. | | | 2) INDICATE ON BOTH SETS OF PLANS THE TYPE OF FLOORING | | | THAT IS BEING INSTALLED. THE PERMIT APPLICATION STATES" | | | NEW FLOORING."WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) TWO DIFFERENT DOCUMENTS HAVE BEEN SUBMITTED FOR | | | FLOORING UNDERLAYMENT.ONE IS FOR "FLOORMUFFLER" AND THE | | | OTHER IS FOR "SENTINEL". WHICH PRODUCT IS PLANNED ON | | | BEING USED? CLARIFY. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) THE FLOOR UNDRELAYMENT SHALL COMPLY WITH THE | | | REQUIREMENTS OF THE 2017 FBC SEC. 1207.2 FOR AIR-BORNE | | | SOUND FOR THE TYPE OF FLOORING MATERIAL BEING | | | INSTALLED. | | | 5) THE FLOOR UNDERLAYMENT SHALL COMPLY WITH THE | | | REQUIREMENTS OF 2017 FBC SEC.1207.3 FOR STRUCTURE-BORNE | | | SOUND FOR THE TYPE OF FLOORING MATERIAL BEING | | | INSTALLED. | | | 6) SUBMIT TWO COPIES OF THE NONCOMBUSTIBILITY TEST FOR | | | THE UNDERLAYMENT AS REQUIRED BY 2017 FBC SECS.703.5.1 | | | AND 703.5.2. | | | 7) SHOW THE WALL AREAS ON THE PLANS WHERE THE DRYWALL | | | WILL BE REPLACED AND SHOW THE TYPE OF BACKER BOARD THAT | | | WILL BE INSTALLED IN THE SHOWER AREA. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|