2019-02-21 11:29:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW: DENIED
 A. SCOPE OF WORK IS GREATER THAN NOTED ON THE PERMIT
 APPLICATION AND VALUE APPEARS TO BE LOW. SCOPE APPEARS
 TO BE AT LEAST A MINIMUM, REMOVAL OF EXISTING KITCHEN
 TYPE SINK, ADDING A THREE COMPARTMENT SINK AND HAND
 SINK AS WELL AS REPLACING AN EXISTING WATER COOLER AND
 WATER HEATER. PLEASE REVISE APPLICATION AND PROVIDE A
 VALUE THAT REFLECTS THE WORK TO BE DONE. A REVIEW OF
 COMMENTS BELOW SHOULD ALSO BE USED TO HELP DEFINE THE
 SCOPE AND VALUE.PLEASE NOTE, THE VALUE IS TO REFLECT
 THE COST OF THE TOTAL PROJECT.
 B. PER WPB FBC 107.2.1 AND/OR WPB FBC 107.3.5.1.3,
 PROVIDE THE FOLLOWING:
 1. A CODE COMPLIANT SANITARY RISER DIAGRAM AND WATER
 RISER DIAGRAM, SHOWING THE EXTENT OF THE NEW WORK. SHOW
 IN FLOOR PLAN AS WELL.
 2. NEW THREE COMPARTMENT SINK SHALL DISCHARGE THROUGH
 AN INDIRECT WASTE IN ACCORDANCE WITH FBC PL 802. SHOW
 ON PLUMBING PLANS AND PROVIDE A DETAIL SHOWING
 COMPLIANCE WITH FBC PL 802.1 AND 802.2 AS APPLICABLE.
 3. IS THE ORIGINAL DRINKING FOUNTAIN ADJACENT TO THE
 TOILET ROOM TO REMAIN IN PLACE? PLEASE CLARIFY ON
 PLANS. PROVIDE A DETAIL SHOWING COMPLIANCE WITH FBC ACC
 306 AND 602 FOR THE NEW ADA COMPLIANT WATER COOLER IS
 IN A DIFFERENT LOCATION FROM THE REPLACED EXISTING
 WATER COOLER. SHOW ON PLUMBING PLANS AND
 4. PROVIDE HOT WATER RECIRC PUMP AND HOT WATER RETURN
 TO COMPLY WITH FBC PL 607.2. PROVIDE SPEC (HP,
 ELECTRICAL CHARACTERISTICS, SIZE) AND DETAIL.
 5. PROVIDE WATER HEATER SPEC (STORAGE CAPACITY AND
 ELECTRICAL CHARACTERISTICS) AND DETAIL, SHOWING
 COMPLIANCE WITH THE REQUIREMENTS OF FBC PL CHAPTER 5
 AND FBC PL 607.3 THERMAL EXPANSION CONTROL. PROVIDE
 SIZING OF THERMAL EXPANSION CONTROL DEVICE.
 6. A MOP SINK IS REQUIRED PER FBC PL TABLE 403.1.
 PROVIDE, OR IF ONE IS IN PLACE THEN IDENTIFY ON THE
 PLANS.
 7. PROVIDE TEMPERED WATER FOR LAVATORIES AS APPLICABLE
 PER FBC 416.5.
 8. EXISTING ADA TOILET ROOMS SHALL CONFORM TO FBC ACC
 SECTIONS 304, 604 AND 606. CONFIRM AND PROVIDE A NOTE
 STATING SAID COMPLIANCE.
  
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS,
 ESPECIALLY AS A RESULT OF RESPONSE TO BUILDING REVIEW
 COMMENTS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  