2019-02-27 10:03:581ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19011369
 2/27/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC FP- FLORIDA FIRE PREVENTION CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 IN ADDITION TO THE CODES IN EFFECT LISTED ABOVE, THE
 PROPOSED PROJECT SHALL ALSO BE IN COMPLIANCE WITH NFPA
 37- 2015 AND THE FLORIDA FIRE PREVENTION CODE SIXTH
 EDITION 2017- SEE SECTIONS 915.1 AND 1301.1 OF THE FBC
 M,
  
 PLEASE REVIEW THE COMMENTS LISTED BELOW, AND CORRECT
 THE PLANS ACCORDINGLY.
  
 1) PROVIDE ENLARGED DIMENSIONED DRAWINGS OF THE
 GENERATOR ROOM DRAWN TO A MINIMUM 1/8" SCALE SHOWING
 THE LOCATIONS OF THE NEW TANK, EXISTING GENERATOR AND
 ALL OTHER ASSOCIATED EQUIPMENT INCLUDING EMERGENCY
 ELECTRICAL PANELS ETC. PLEASE PROVIDE ON THE DRAWINGS:
 A) FIRE SPRINKLER DESIGN SPECIFICATIONS. B)
 FIRE-RESISTANCE RATING OF THE WALLS, FLOOR AND CEILING
 ENCLOSING THE ROOM. C) FIRE-RESISTANCE RATING OF THE
 EXISTING DOOR. D) REQUIRED INSTALLATION CLEARANCES FOR
 ALL EQUIPMENT. E) FUEL AND VENT PIPING RUNS AND
 SPECIFICATIONS INCLUDING FILL PIPING LOCATIONS. E)
 LOCATIONS OF EXISTING VENTILATION FANS AND OTHER
 VENTILATION OPENINGS AND EXHAUST OUTLETS- SEE
 SECTION107.2.1. WPB, AND SECTION 66.9.7 FBC FP.
  
 2) REFER TO SECTION AND TABLE 66.9.6.1 FBC FP AND
 PROVIDE THE FLAMMABLE LIGUID CLASS OF THE FUEL OIL AND
 THE TOTAL AMOUNT OF LIQUID TO BE INSTALLED IN THE
 GENERATOR ROOM. THE TOTAL AMOUNT SHALL INCLUDE THE
 GALLON CAPACITY OF THE GENERATOR'S INTEGRAL BELLY TANK
 (IF APPLICABLE).
  
 3) CLARIFY HOW CONTAINMENT, DRAINAGE, AND SPILL CONTROL
 ARE BEING PROVIDED FOR THE TANK- REFER TO SECTION
 66.9.13 FBC FP AND PROVIDE DETAILS AND NOTES ON THE
 PLAN.
  
 4) CLARIFY HOW ADEQUATE VENTILATION WILL BE PROVIDED
 FOR THE GENERATOR/TANK ROOM. SEE SECTION 24.10 NFPA
 30-2015 AND PROVIDE A VENTILATION SYSTEM IN COMPLIANCE,
 OR VERIFY THE EXISTING SYSTEM IS IN COMPLIANCE. (CODE
 REFERENCES: SECTION 11.7.5.2 FBC FP WHICH REFERENCES
 NFPA 110 FOR EMERGENCY GENERATORS AND SECTION 7.9.1.1
 NFPA 110- 2016 WHICH REFERENCES NFPA 30 FOR
 INSTALLATION OF THE FUEL TANK IN THE GENERATOR ROOM).
  
 5) REFER SECTION 66.9.12.1 FBC FP AND VERIFY THE
 ELECTRICAL SYSTEMS IN THE GENERATOR/TANK ROOM ARE IN
 COMPLIANCE.
  
 6) PLEASE NOTE THAT THE SUBMITTED REDUCED-IN- SIZE
 ARCHITECTURAL PLANS BY QUINCY JOHNSON ARCHITECTS CAN BE
 USED FOR REFERENCE ONLY BECAUSE THEY DO NOT BEAR THE
 ORIGINAL SIGNATURE AND SEAL OF THE ARCHITECT OF RECORD-
 SECTION 61G14-16.003 FAC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  