| Plan Review Notes For Permit 19011359 |
| Permit Number |
19011359 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-24 16:58:37 | 1) ) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | 2) EXISTING PLANS ON FILE WITH THE CITY SHOW THE TOTAL | | | BTU ON THIS GAS SYSTEM AS 829,000 BTU'S AND THE | | | SUBMITTED GAS PLAN SHOWS A TOTAL BTU LOAD OF 725,000 | | | BTU'S. REVISE THE BTU LOAD ON THE SUBMITTED GAS PLAN. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|