Plan Review Notes
Plan Review Notes For Permit 19011247
Permit Number 19011247
Review Stop B
Sequence Number 5
Notes
Date Text
2019-05-21 09:37:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19011247
 ADD: 2400 PRESIDENTIAL WAY, SUITE: 1105
 CONT: SUNSTREAM BUILDING ENTERPRISE
 TEL: 954-234-0892
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: TUESDAY MAY 21, 2019
 ACTION: DENIED
  
 1) OK
  
 2) OK.
  
 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST
 REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE
 FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE
 WITH:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 RESPONSE:
 TEST REPORT SUBMITTED IS NOT DONE IN ACCORDANCE WITH
 ASTM E492 AS REQUIRED BY SEC. 1207.3 AND DOESN'T
 PROVIDE THE IIC RESULTS.
  
  
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 RESPONSE:
 NO SUBMITTED AT ALL.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 RESPONSE:
 REPEAT COMMENT. FIVE TIMES. COPY OF TESTING FOR
 PROPOSED INSULATION WAS NOT SUBMITTED.
  
  