| Date |
Text |
| 2019-04-09 09:45:28 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19011247 |
| | ADD: 2400 PRESIDENTIAL WAY, SUITE: 1105 |
| | CONT: SUNSTREAM BUILDING ENTERPRISE |
| | TEL: 954-234-0892 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. FEB. 11/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA LIST |
| | THE: |
| | |
| | ORIGINAL COMMENT: |
| | 1A) OCCUPANCY TYPE AS R-3. PLEASE NOTE UNDER THE 2017 |
| | FBC-B SECTION 310.5 IS FOR SINGLE FAMILY DWELLINGS NOT |
| | FOR UNITS IN HIGHRISE BUILDINGS. SECTION 310.4 LIST |
| | APARTMENTS (LONG TERM NON-TRANSIENT)AND CONDOS AS R2 |
| | UNITS, PLEASE UPDATE PLANS. |
| | |
| | RESPONSE: |
| | DESIGN CRITERIA STILL SHOWS R3 OCCUPANCY. THIS IS |
| | INCORRECT AGAIN. R3 OCCUPANCY IS ONLY FOR ONE AND TWO |
| | FAMILY DWELLINGS NOT CONDOMINIUMS. REVISE ORIGINAL |
| | PLAN. PROVIDE CORRECT INFORMATION AND WHITE-OUT IS NOT |
| | ALLOWED. SEE SEC. 310.4 FBC AND REVISE AS REQUIRED. |
| | |
| | 1B) OK. |
| | |
| | 1C) OK. |
| | |
| | 2) OK. |
| | |
| | ORIGINAL COMMENT: |
| | 3) SHEET 1-1 UNDER THE HEADING SCOPE OF WORK LIST |
| | REMOVE EXISTING FLOOR TILES AND INSTALL NEW LAMINATE |
| | FLOOR OVER SOUND INSULATION. PLEASE SHOW CONFORMANCE |
| | WITH: |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2017) |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. COPY OF TESTING FOR PROPOSED INSULATION |
| | WAS NOT SUBMITTED. |
| | |
| | 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. COPY OF TESTING FOR PROPOSED INSULATION |
| | WAS NOT SUBMITTED. |
| | |
| | 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. COPY OF TESTING FOR PROPOSED INSULATION |
| | WAS NOT SUBMITTED. |
| | |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |
| | |