| 2019-02-25 17:23:18 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19011234 |
| | 2/25/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMISSIONING OF THE NEW HVAC SYSTEMS IS REQUIRED |
| | PER SECTION C408.2 FBC-17 ENERGY CONSERVATION. SUBMIT A |
| | COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND |
| | DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE |
| | THAT A COPY OF THE COMMISSIONING REPORT SHALL BE |
| | SUBMITTED FOR REVIEW AT FINAL INSPECTION. |
| | |
| | 2) SHOW THE LOCATIONS OF THE REQUIRED DUCT SMOKE |
| | DETECTORS IN THE SUPPLY AIR SYSTEMS OF THE NEW AIR |
| | HANDLERS- SECTION 606.2.1 FBC M |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |