2019-03-04 13:21:051) ALL HOSE BIBBS SHALL BE SEPARATELY VALVED PER 2017
 FBC-PLUMBING SEC.606.2 (2).
 2) SHT. SP-1 SHOWS THE VAK-PAK WASTE TO THE STORM
 DRAINAGE SYSTEM. ONLY STORMWATER MAY DISCHARGE INTO THE
 CITY'S STORM DRAINAGE SYSTEM PER CITY OF WPB CODE OF
 ORDINANCES CHAPTER 90, ARTICLE V, SEC. 90-203. CONTACT
 MANNY GONZALEZ IN THE ENGINEERING DEPT. AT
 561-494-1040.
 3) SHT. 5 OF 7 - NOTES REFER TO THE FIFTH EDITION OF
 THE FLORIDA BUILDING CODE. THE CODE IN EFFECT IS THE
 6TH EDITION. REVIS EHTE NOTE.
 4) SHT. PPD-1 - PLUMBING NOTES #1 REFERS TO THE 2014
 FBC. THE CODE IN EFFECT IS THE 2017 FBC. PLEAS REVISE
 THE NOTE.
  