| Plan Review Notes For Permit 19011159 |
| Permit Number |
19011159 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-29 10:16:23 | | | | | | | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | | FBC-RES. SEC.G 2407.1.2ND REQUEST. | | | | | | 2) GAS APPLIANCES SHALL BE LISTED AND LABELED. FBC-RES. | | | SEC.G2408.1. SUBMIT MANUFACTURER'S SPECIFICATIONS THAT | | | SHOW THE RANGE IS LISTED AND LABELED. THE SUBMITTED | | | SHEETS ARE FROM AN INSTALLATION MANUAL AND DO NOT SHOW | | | THE UNIT IS LISTED AND LABELED. | | | | | | 3) THE FLOOR PLAN SHOWS THE RANGE AS 200 MBH BUT THE | | | GAS RISER SSHOWS THE RANGE AS 120 MBH. CLARIFY. IF THE | | | RANGE IS 200 MBH, THE 3/4 INCH LINE FROM THE METER IS | | | UNDERSIZED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|