| Date |
Text |
| 2019-04-23 11:17:12 | GAS 1ST REVIEW**DENIED**04/23/2019 |
| | |
| | 1) PLAN THAT BEAR THE DESIGN PROFESSIONAL NAME, |
| | LICENSE, AND OR TITLE BLOCK ARE REQUIRED TO BE WET |
| | SIGN. NONE OF THE PAGES SUBMITTED ARE SIGNED. FAC |
| | 61G15-23.001 |
| | |
| | 2) PROVIDE MAKE UP AIR CALCULATION FOR THE KITCHEN |
| | STOVE. FBC 107.3.5. FBCG 403.9.3 |
| | |
| | 3) PROVIDE LOCATION OF SHUT OFF VALVE THAT WILL ALLOW |
| | READY ACEESS. HAVING TO REMOVE THE STOVE UNDER |
| | DEFINITION IS NOT HAVING READY ACCESS. FBC 107.2.1 |
| | |
| | 4) SHT G-1 ON PLAN KEY NOTES #2 REFERS TO SHT P-1 FOR |
| | WATER HEATER SPECIFICATIONS. NO SHT P-1 WAS SUBMITTED. |
| | SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |