| Plan Review Notes For Permit 19011075 |
| Permit Number |
19011075 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-07-09 08:26:01 | ELECTRICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 3RD REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | THE FOLLOWING IS A RE-PEAT COMMENT FROM PREVIOUS REVIEW | | | | | | 1. PROVIDE SERVICE OUTLET FOR MECHANICAL EQUIPMENT AT | | | GUEST HOUSE. | | | E3901.12 | | | | | | THE FOLLOWING ARE NEW COMMENTS | | | | | | 1. FEEDER SERVICE AT GUEST HOUSE REQUIRES TWO (2) | | | GROUND RODS. | | | E3607.3 | | | | | | 2. FEEDER SERVICE AT GUEST HOUSE REQUIRES MAIN MEANS OF | | | DISCONNECT. | | | E3706.3 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | | | | | | | | | | | | | |
|