Plan Review Notes
Plan Review Notes For Permit 19011075
Permit Number 19011075
Review Stop P
Sequence Number 2
Notes
Date Text
2019-05-30 17:20:13PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 1. PLUMBING PLANS DO NOT REFLECT WHAT IS ON FILE WITH
 THE CITY OF WEST PALM BEACH. I HAVE INCLUDED A COPY OF
 PLAN PAGE P-1 FROM PERMIT # 15120126 THAT SHOULD
 REFLECT THE EXISTING PLUMBING AT THIS RESIDENCE.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE A PLUMBING SANITARY SYSTEM RISER DIAGRAHM OF
 THE PROPOSED BUILDING SEWER. INCLUDE THAT PORTION OF
 THE SYSTEM THAT WILL REMAIN AS-IS.
 PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION
 107.3.5.3 (12).
  
 3. PLEASE PLACE NOTE ON PLAN. THE MASTER BATH TUB
 AND/OR SHOWER VALVE SHALL COMPLY WITH FBC RES P2713.3
 BATHTUB AND WHIRLPOOL BATHTUB VALVES AND P2708.4SHOWER
 CONTROL VALVES.
 HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS
 SHALL BE LIMITED TO A TEMPERATURE OF NOT GREATER THAN
 120?F (49?C) BY A WATER TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE
 SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION
 TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION P2708.3.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  