| 2019-05-30 17:20:13 | PLUMBING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 2ND REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| | EDITION |
| | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1. PLUMBING PLANS DO NOT REFLECT WHAT IS ON FILE WITH |
| | THE CITY OF WEST PALM BEACH. I HAVE INCLUDED A COPY OF |
| | PLAN PAGE P-1 FROM PERMIT # 15120126 THAT SHOULD |
| | REFLECT THE EXISTING PLUMBING AT THIS RESIDENCE. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PROVIDE A PLUMBING SANITARY SYSTEM RISER DIAGRAHM OF |
| | THE PROPOSED BUILDING SEWER. INCLUDE THAT PORTION OF |
| | THE SYSTEM THAT WILL REMAIN AS-IS. |
| | PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION |
| | 107.3.5.3 (12). |
| | |
| | 3. PLEASE PLACE NOTE ON PLAN. THE MASTER BATH TUB |
| | AND/OR SHOWER VALVE SHALL COMPLY WITH FBC RES P2713.3 |
| | BATHTUB AND WHIRLPOOL BATHTUB VALVES AND P2708.4SHOWER |
| | CONTROL VALVES. |
| | HOT WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS |
| | SHALL BE LIMITED TO A TEMPERATURE OF NOT GREATER THAN |
| | 120?F (49?C) BY A WATER TEMPERATURE LIMITING DEVICE |
| | THAT CONFORMS TO ASSE 1070 OR CSA B125.3, EXCEPT WHERE |
| | SUCH PROTECTION IS OTHERWISE PROVIDED BY A COMBINATION |
| | TUB/SHOWER VALVE IN ACCORDANCE WITH SECTION P2708.3. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |