| Date |
Text |
| 2019-01-29 15:31:07 | CODES IN EFFECT: |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 5TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | PLUMBING COMMENTS:DENIED |
| | |
| | 1. PLANS DO NOT DESCRIBE PRE-EXISTING CONDITIONS.CAN |
| | NOT TELL IF FIXTURES HAVE BEEN RELOCATED FROM ORIGINAL |
| | POSITIONS REQUIRING RECONFIGURATION OF PIPING SYSTEMS. |
| | PROVIDE A DETAILED SCOPE OF WORK AND AN "EXISTING FLOOR |
| | PLAN" IF FIXTURE LOCATIONS ARE RECONFIGURED PER WPB FBC |
| | 107.2.1. IF FIXTURES SUCH AS TOILETS, SINKS AND |
| | LAVATORIES ARE GOING BACK INTO SAME LOCATIONS, PROVIDE |
| | A NOTE STATING "CONNECT NEW FIXTURES TO EXISTING |
| | PLUMBING ROUGH"; FOR THE BATHTUB PROVIDE A NOTE STATING |
| | "PROVIDE NEW IN-WALL CONTROL VALVE AND TRIM". IF |
| | FIXTURE LOCATIONS ARE TO BE RECONFIGURED THEN PROVIDE A |
| | SANITARY RISER DIAGRAM PER WPB FBC 107.3.5.3 (12). |
| | 2. THE PLANS SHALL BEAR THE NAME OF THE DESIGNER AND |
| | HIS SIGNATURE PER WPB FBC 107.2.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | 561-805-6715 |
| | [email protected] |