| 2019-06-12 10:05:03 | PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH |
| | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1) VALUE STILL APPEARS TOO LOW. PROVIDE ACTUAL SIGNED |
| | CONTRACTS NOT EMAILS OF EST. THE PLUMBING FIXTURES, ADA |
| | LIFT AND DESIGN COST HAVE NOT BEEN INCLUDED IN YOUR |
| | VALUATION SUBMITTAL. WPB AMEND 109.3 |
| | |
| | 2) PLANS SUBMITTED ARE NOT SIGNED AND SEALED BY DESIGN |
| | PROFESSIONAL. THE EXISTING FLOOR PLAN LAY OUT HAS BEEN |
| | REMOVED.F.S 471, 481 |
| | |
| | 3) TANKLESS WATER HEATER INSTALLATION MANUAL CALLS OUT |
| | ONLY A 10F HEAT RISE PRODUCING A MAX 90F OF HOT WATER @ |
| | 2GPM. PER FBC-P 607.1 HOT WATER SHALL BE REQUIRED. HOT |
| | WATER IS DEFINED AS 110F OR GREATER. SUBMIT A TANKLESS |
| | WATER HEATER WITH A MIN OF 30F HEAT RISE @ 2GPM. FBC-P |
| | 604.3. PLEASE NOTE BY CHANGING THE KW OF THE HWH THE |
| | ELC DEMAND AND WIRE SIZE WILL INCREASE. PLEASE BE SURE |
| | TO REVISE THE ELC LOAD AND PLAN ACCORDINGLY. |
| | |
| | 4) PROVIDE CLEAR FLOOR SPACE, TUNING SPACE, AND |
| | ACCESSIBLE ROUTE OF AND TO THE BREAK ROOM SINK. ALL |
| | ELEMENTS SHALL MEET FLORIDA ACCESSIBILITY. 606.2, 305, |
| | 402, 403 |
| | |