| 2019-05-20 14:07:38 | ***CORRECTIONS*** |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 2ND BUILDING PLAN REVIEW DENIED: |
| | |
| | (THE COMMENTS FROM ITEM #1 OF THE 1ST REVIEW, NOTED |
| | BELOW, STILL HAVE NOT BEEN CORRECTED.) |
| | 1. THE SUBMITTED SHEET A?1 DOES NOT INDICATE WHO THE |
| | DESIGNER OF THE PLAN IS? |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | (THE COMMENTS FROM ITEM #2 OF THE 1ST REVIEW, NOTED |
| | BELOW, STILL HAVE NOT BEEN CORRECTED.) |
| | 2. THE SUBMITTED SHEET A?1 DOES NOT COMPLY WITH RECORD |
| | RETENTION STANDARDS FOR SCANNING. 107.2.1.3 QUALITY OF |
| | BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A |
| | MINIMUM 1/8 INCH SCALE. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | (THE COMMENTS FROM ITEM #3 OF THE 1ST REVIEW, NOTED |
| | BELOW, ONLY HAVE CORRECTIONS IN ONE DETAILED SECTION OF |
| | SHEET A-1. THE OTHER DETAILED SECTIONS OF SHEET A-1 |
| | NEED TO BE CORRECTED.) |
| | 3. SHEET A?1 DETAIL # 1 CABINET ELEVATION SHOWS A |
| | MICROWAVE ON A SHELF WITH THE BOTTOM OF THE MICROWAVE |
| | AT A HEIGHT OF 4 FOOT 10 INCHES OR AT 58 INCHES ABOVE |
| | FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE 2017 |
| | FBC?ACCESSIBILITY CODE SECTIONS: 308 REACH RANGES. |
| | 308.2 FORWARD REACH./ 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | MAXIMUM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | |