| Plan Review Notes For Permit 19011027 |
| Permit Number |
19011027 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-23 08:11:54 | 1-THE SHEET FROM NFPA 58 IS ILLEGIBLE, SUBMIT A LEGIBLE | | | SHEET FROM NFPA 58 PER 2017 FBC WPB AMENDMENTS 107.2.1 | | | 2-THE ANODE SHEET IS ILLEGIBLE, SUBMIT A LEGIBLE ANODE | | | SHEET FROM NFPA 58 PER 2017 FBC WPB AMENDMENTS 107.2.1 | | | 3-THE REGULATOR SHEET IS BLURRY, SUBMIT A LEGIBLE | | | REGULATOR SHEET FROM NFPA 58 PER 2017 FBC WPB | | | AMENDMENTS 107.2.1 | | | 4- PLEASES INDICATE THE SIZE OF THE PIPE DOWNSTREAM OF | | | THE REGULATOR FOR THE GENERATOR. | | | 5-THE TANK REQUIRES TRAFFIC PROTECTION WITHIN 10' OF | | | THE DRIVEWAY PER NFPA 58- PLEASE SHOW THE TYPE OF | | | PROTECTION ON THE PLAN PER NFPA SEC. 666.1 | | | 6-PLEASE SUBMIT TWO COPIES OF THE GENERATORS | | | MANUFACTURES SPECIFICATIONS. | | | 7-THE SIZING TABLE PROVIDED IS FROM 2014 AND IS AN | | | OUTDATED CODE SECTION, PLEASE SUBMIT TABLE FROM CURRENT | | | 2017 FBC FUEL GAS CODE. | | | 8-PLEASE SUBMIT TWO COPIES OF THE ALL DOCUMENTS PER WPB | | | AMENDMENTS SEC.107.1 |
|