Plan Review Notes
Plan Review Notes For Permit 19011027
Permit Number 19011027
Review Stop G
Sequence Number 1
Notes
Date Text
2019-02-23 08:11:541-THE SHEET FROM NFPA 58 IS ILLEGIBLE, SUBMIT A LEGIBLE
 SHEET FROM NFPA 58 PER 2017 FBC WPB AMENDMENTS 107.2.1
 2-THE ANODE SHEET IS ILLEGIBLE, SUBMIT A LEGIBLE ANODE
 SHEET FROM NFPA 58 PER 2017 FBC WPB AMENDMENTS 107.2.1
 3-THE REGULATOR SHEET IS BLURRY, SUBMIT A LEGIBLE
 REGULATOR SHEET FROM NFPA 58 PER 2017 FBC WPB
 AMENDMENTS 107.2.1
 4- PLEASES INDICATE THE SIZE OF THE PIPE DOWNSTREAM OF
 THE REGULATOR FOR THE GENERATOR.
 5-THE TANK REQUIRES TRAFFIC PROTECTION WITHIN 10' OF
 THE DRIVEWAY PER NFPA 58- PLEASE SHOW THE TYPE OF
 PROTECTION ON THE PLAN PER NFPA SEC. 666.1
 6-PLEASE SUBMIT TWO COPIES OF THE GENERATORS
 MANUFACTURES SPECIFICATIONS.
 7-THE SIZING TABLE PROVIDED IS FROM 2014 AND IS AN
 OUTDATED CODE SECTION, PLEASE SUBMIT TABLE FROM CURRENT
 2017 FBC FUEL GAS CODE.
 8-PLEASE SUBMIT TWO COPIES OF THE ALL DOCUMENTS PER WPB
 AMENDMENTS SEC.107.1