Plan Review Notes
Plan Review Notes For Permit 19011020
Permit Number 19011020
Review Stop M
Sequence Number 2
Notes
Date Text
2019-03-07 07:58:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19011020
 3/7/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) TTHE SUBMITTED SUMMARY LOAD CALCULATIONS MUST BE
 SIGNED AND SEALED BY A FL. REGISTERED ENGINEER. PLEASE
 PROVIDE THE AREA IN SQ. FT. OF THE ZONE ON THE
 RESUBMITTED CALCULATION.
  
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS ASSOCIATED WITH HEATING, VENTILATING AND
 AIR CONDITIONING OF THE BUILDING SHALL BE DETERMINED IN
 ACCORDANCE WITH ANSI/ASHRAE/ACCA STANDARD 183 OR ACCA
 MANUAL N OR BY AN APPROVED EQUIVALENT COMPUTATIONAL
 PROCEDURE USING THE DESIGN PARAMETERS SPECIFIED IN
 CHAPTER 3. HEATING AND COOLING LOADS SHALL BE ADJUSTED
 TO ACCOUNT FOR LOAD REDUCTIONS THAT ARE ACHIEVED WHERE
 ENERGY RECOVERY SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM
 IN ACCORDANCE WITH THE ASHRAE HVAC SYSTEMS AND
 EQUIPMENT HAND-BOOK BY AN APPROVED EQUIVALENT
 COMPUTATIONAL PROCEDURE. DESIGN LOADS SHALL BE ATTACHED
 TO THE CODE COMPLIANCE FORM SUBMITTED TO THE BUILDING
 DEPARTMENT WHEN THE BUILDING IS PERMITTED OR, IN THE
 EVENT THE MECHANICAL PERMIT IS OBTAINED AT A LATER
 TIME, THE SIZING CALCULATION SHALL BE SUBMITTED WITH
 THE APPLICATION FOR THE MECHANICAL PERMIT.
  
 EXCEPTION: WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A
 REGISTERED ENGINEER, THE ENGINEER HAS THE OPTION OF
 SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE
 BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING
 CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE
 FOLLOWING (BY ZONE):
  
 1.PROJECT NAME/OWNER
  
 2.PROJECT ADDRESS
  
 3.AREA IN SQUARE FEET
  
 4.SIZING METHOD USED
  
 5.OUTDOOR DRY BULB USE
  
 6.INDOOR DRY BULB
  
 7.OUTDOOR WET BULB USED
  
 8.GRAINS WATER (DIFFERENCE)
  
 9.TOTAL SENSIBLE GAIN
  
 10.TOTAL LATENT GAIN
  
 11.RELATIVE HUMIDITY
  
 12.TOTAL COOLING REQUIRED WITH OUTSIDE AIR
  
 2) AN AIR DISTRIBUTION PLAN IS ATTACHED TO THE
 CALCULATION FORM WHICH IS NOT ACCEPTABLE FOR REVIEW PER
 SECTION 105.3.1.2 WPB WHICH REQUIRES THE PLAN TO BE
 DRAWN BY A FL. LICENSED ENGINEER OF THE INSTALLING
 CONTRACTOR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  