| 2019-03-07 07:58:54 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19011020 |
| | 3/7/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) TTHE SUBMITTED SUMMARY LOAD CALCULATIONS MUST BE |
| | SIGNED AND SEALED BY A FL. REGISTERED ENGINEER. PLEASE |
| | PROVIDE THE AREA IN SQ. FT. OF THE ZONE ON THE |
| | RESUBMITTED CALCULATION. |
| | |
| | C403.2.1 CALCULATION OF HEATING AND COOLING LOADS. |
| | DESIGN LOADS ASSOCIATED WITH HEATING, VENTILATING AND |
| | AIR CONDITIONING OF THE BUILDING SHALL BE DETERMINED IN |
| | ACCORDANCE WITH ANSI/ASHRAE/ACCA STANDARD 183 OR ACCA |
| | MANUAL N OR BY AN APPROVED EQUIVALENT COMPUTATIONAL |
| | PROCEDURE USING THE DESIGN PARAMETERS SPECIFIED IN |
| | CHAPTER 3. HEATING AND COOLING LOADS SHALL BE ADJUSTED |
| | TO ACCOUNT FOR LOAD REDUCTIONS THAT ARE ACHIEVED WHERE |
| | ENERGY RECOVERY SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM |
| | IN ACCORDANCE WITH THE ASHRAE HVAC SYSTEMS AND |
| | EQUIPMENT HAND-BOOK BY AN APPROVED EQUIVALENT |
| | COMPUTATIONAL PROCEDURE. DESIGN LOADS SHALL BE ATTACHED |
| | TO THE CODE COMPLIANCE FORM SUBMITTED TO THE BUILDING |
| | DEPARTMENT WHEN THE BUILDING IS PERMITTED OR, IN THE |
| | EVENT THE MECHANICAL PERMIT IS OBTAINED AT A LATER |
| | TIME, THE SIZING CALCULATION SHALL BE SUBMITTED WITH |
| | THE APPLICATION FOR THE MECHANICAL PERMIT. |
| | |
| | EXCEPTION: WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A |
| | REGISTERED ENGINEER, THE ENGINEER HAS THE OPTION OF |
| | SUBMITTING A SIGNED AND SEALED SUMMARY SHEET TO THE |
| | BUILDING DEPARTMENT IN LIEU OF THE COMPLETE SIZING |
| | CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE |
| | FOLLOWING (BY ZONE): |
| | |
| | 1.PROJECT NAME/OWNER |
| | |
| | 2.PROJECT ADDRESS |
| | |
| | 3.AREA IN SQUARE FEET |
| | |
| | 4.SIZING METHOD USED |
| | |
| | 5.OUTDOOR DRY BULB USE |
| | |
| | 6.INDOOR DRY BULB |
| | |
| | 7.OUTDOOR WET BULB USED |
| | |
| | 8.GRAINS WATER (DIFFERENCE) |
| | |
| | 9.TOTAL SENSIBLE GAIN |
| | |
| | 10.TOTAL LATENT GAIN |
| | |
| | 11.RELATIVE HUMIDITY |
| | |
| | 12.TOTAL COOLING REQUIRED WITH OUTSIDE AIR |
| | |
| | 2) AN AIR DISTRIBUTION PLAN IS ATTACHED TO THE |
| | CALCULATION FORM WHICH IS NOT ACCEPTABLE FOR REVIEW PER |
| | SECTION 105.3.1.2 WPB WHICH REQUIRES THE PLAN TO BE |
| | DRAWN BY A FL. LICENSED ENGINEER OF THE INSTALLING |
| | CONTRACTOR. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |