2019-04-01 14:44:25PLUMBING 2ND REVIEW**DENIED**
  
 1) PROVIDE TANKLESS WATER HEATER COMPLETE INSTALLATION
 MANUAL. PROVIDE SPEC AND LISTING FOR APPROVED ASSE 1070
 TEMPERING DEVICE. FBC 107.3.5, FBC P607.1.2
  
 2)TRAILER PLANS 12 X 56 #2 NOTE CALLS OUT OF ALL
 PLUMBING, WALLS AND DOORS BE SITE INSTALLED. THE
 INTERIOR RESTROOM WOULD NOW BE REQUIRED TO COMPLY WITH
 THE FBC PLUMBING AND ACCESSIBILITY CODE 2017 6TH
 ED.PROVIDE PLANS SHOWING HOW YOU INTEND TO COMPLY WITH
 THE ACCESSIBILITY REQUIREMENTS FOR A TOILET ROOM TO
 INCLUDE CLEAR FLOOR SPACES, TURNING SPACE, ETC
  
 3) PROVIDE HOW THE CITY'S DOMESTIC AND SITE POTABLE
 WATER SUPPLY IS GOING TO BE PROTECTED AS REQUIRED IN
 FBC P 608.1
  
 4) PROVIDE HOLDING TANKS PUMP OUT SCHDULE AND CONTRACT.
 FBC 107.2.1
  