| 2019-02-20 15:31:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM SHOWS A 208/120 VOLT SERVICE FROM FPL. |
| | THIS SERVICE GOES TO A METER CAN, THEN DISCONNECT, AND |
| | THEN FEEDS A TRANSFORMER SHOWING THAT IT BECOMES |
| | 208/120 VOLT. IF THE SERVICE IS ALREADY 208/120 VOLT, |
| | WHY WOULD T HIS TRANSFORMER BE NEEDED? IS PART OF THIS |
| | SERVICE 480/277 VOLT? PROVIDE CLARIFICATION AND/OR |
| | CORRECTIONS TO RISER DIAGRAM AS NEEDED. NEC 215.5; WPB |
| | FBC 107.2.1 |
| | 2. ESTIMATED VALUES FOR AIC CALCULATION IS NOT |
| | ACCEPTABLE. PROVIDE ACCURATE AVAILABLE SHORT CIRCUIT |
| | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE |
| | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| | CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC |
| | RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, |
| | 110.10 |
| | 3. GROUNDING OF SEPARATLEY DERIVED SYSTEMS WOULD BE |
| | ACCOMPLISHED AT THE TRANSFORMER. IT SHOULD NOT BE |
| | DUPLICATED AT THE 100 AMP DISCONNECTS FOR TR1 AND TR2. |
| | PROVIDE CORRECTION. NEC 250.6, NEC 250.30 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |