Notes
Date Text
2019-01-31 04:48:031) INDICATE ON THE PLAN IF THE DRAIN FROM THE TUB IS
 BEING RELOCATED. IF IT IS, SUBMIT DETAILS FOR THE FIRE
 STOPPING OF THE PENETRATION TO ENSURE THE REQUIRED FIRE
 RATING OF THE EXISTING SLAB IS MAINTAINED.
 2) INDICATE THE TYPE OF PIPE BEING INSTALLED FOR THE
 SHOWER. PVC MAY NOT BE PERMITTED DEPENDING ON WHETHER
 THE PIPING IS LOCATED IN A RETURN AIR PLENUM AND MUST
 ALSO COMPLY WITH 2017 FBC-BUILDING SEC.718.5.
 3) THE NEW SHOWER VALVE SHALL COMPLY WITH 2017
 FBC-PLUMBING SEC.424.3. THE VALVE SHALL BE BALANCED
 PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC.SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VALVE IF AVAILABLE. IF THERE IS
 A HAND-HELD SHOWER, A BACKFLOW PREVENTION DEVICE SHALL
 BE INSTALLED IN ACCORDANCE WITH 2017 FBC-PLUMBING
 SEC.424.2.
  