| Plan Review Notes For Permit 19010946 |
| Permit Number |
19010946 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-01-31 04:48:31 | 1) INDICATE ON THE PLANS IF NEW TILE WILL BE INSTALLED | | | ON THE FLOOR IN THE BATHROOM. IF SO, SUBMIT TWO COPIES | | | OF A TEST REPORT FOR THE UNDERLAYMENT FOR THE TILE | | | SHOWING COMPLIANCE WITH 2017 FBC SEC. 1207.2 FOR | | | AIR-BORNE SOUND TRANSMISSION AND SEC.1207.3 FOR | | | STRUCTURE-BORNE SOUND TRANSMISSION, | | | 2) FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | 3) INDICATE ON THE PLAN THE TYPE OF BACKING BOARD THAT | | | WILL BE INSTALLED FOR THE TILE. WATER-RESISTANT GYPSUM | | | BACKING BOARD SHALL NOT BE USED IN AREAS WHERE THERE | | | WILL BE DIRECT EXPOSURE TO WATER OR IN AREAS SUBJECT TO | | | CONTINUOUS HIGH HUMIDTY. 2017 FBC-BUILDING SEC.2509.3. | | | 4) INDICATE ON THE PLAN IF THE BACK WALL OF THE SHOWER | | | IS A TENANT SEPARATION WALL. IF SO, THE FIRE RATING OF | | | THE WALL SHALL BE MAINTAINED AS REQUIRED BY 2017 FBC - | | | BUILDING SEC. 420.1, 420.2, 708.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|