Plan Review Notes
Plan Review Notes For Permit 19010946
Permit Number 19010946
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-31 04:48:311) INDICATE ON THE PLANS IF NEW TILE WILL BE INSTALLED
 ON THE FLOOR IN THE BATHROOM. IF SO, SUBMIT TWO COPIES
 OF A TEST REPORT FOR THE UNDERLAYMENT FOR THE TILE
 SHOWING COMPLIANCE WITH 2017 FBC SEC. 1207.2 FOR
 AIR-BORNE SOUND TRANSMISSION AND SEC.1207.3 FOR
 STRUCTURE-BORNE SOUND TRANSMISSION,
 2) FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
 3) INDICATE ON THE PLAN THE TYPE OF BACKING BOARD THAT
 WILL BE INSTALLED FOR THE TILE. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL NOT BE USED IN AREAS WHERE THERE
 WILL BE DIRECT EXPOSURE TO WATER OR IN AREAS SUBJECT TO
 CONTINUOUS HIGH HUMIDTY. 2017 FBC-BUILDING SEC.2509.3.
 4) INDICATE ON THE PLAN IF THE BACK WALL OF THE SHOWER
 IS A TENANT SEPARATION WALL. IF SO, THE FIRE RATING OF
 THE WALL SHALL BE MAINTAINED AS REQUIRED BY 2017 FBC -
 BUILDING SEC. 420.1, 420.2, 708.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  