| 2019-02-05 15:30:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: DENIED |
| | PROVIDE THE FOLLOWING PER WPB FBC 107.2.1. |
| | 1. PROVIDE FLOOR PLAN SHOWING LOCATION OF WORK TO BE |
| | PERFORMED. 8-1/2 X 11 SIZE PAPER IS ADEQUATE. |
| | 2. PROVIDE SCOPE NOTING WHAT WORK IS TO BE PERFORMED. |
| | 3. PROVIDE NAME OF DESIGNER WITH SIGNATURE. |
| | 4. PROVIDE ADDRESS OF RESIDENCE ON EACH SUBMITTED |
| | SHEET. |
| | 5. SHEETS SHOULD BE NUMBERED WITH SEQUENCE AND QUANTITY |
| | OF PAGES IE. 1 OF 2, 2 OF 2 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |