| Plan Review Notes For Permit 19010903 |
| Permit Number |
19010903 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-02-19 04:47:45 | 1) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THE PERMIT | | | APPLICATION FOLDER SHOWING TWO DIFFERENT TOTAL BTU | | | LOADS FOR THE GAS SYSTEM. ONE GAS DRAWING SHOWS A TOTAL | | | BTU LOAD OF 215,000 BTU'S AND THE OTHER DRAWING SHOWS A | | | TOTAL BTU LOAD OF 245,000 BTU'S. CLARIFY. REMOVE OLD | | | DRAWINGS FROM THE PERMIT APPLICATION PACKAGE.WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 2) IF THE TOTAL BTU LOAD IS 245,000 THEN THE 1 INCH | | | LINE FROM THE METER IS UNDERSIZED PER SIZING TABLE | | | 402.4 (2). CLARIFY . | | | 3) THE 1/2 INCH LINE TO THE STOVE IS UNDERSIZED. THE | | | LINE SHALL BE A MINIMUM OF 3/4 INCH PER TABLE 402.4 (2) | | | BASED ON THE LENGTH OF 80 FEET. | | | 4) GAS PIPING INSTALLED ACROSS ROOF SURFACES SHALL BE | | | ELEVATED NO LESS THAN 3 1/2 INCHES ABOVE THE ROOF | | | SURFACE. 2017 FBC-FUEL GAS SEC.404.9. PLACE A NOTE ON | | | THE PLANS REFERENCING THIS CODE SECTION. | | | 5) THE MINIMUM SIZE PIPE TO THE TANKLESS WATER HEATER | | | SHALL BE 1 INCH PER TABLE 402.4(2). A 3/4 INCH METALLIC | | | PIPE CAN ONLY CARRY 117,000 BTU'S UNDER THE 80 FEET ROW | | | IN THE GAS TABLE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|