| Plan Review Notes For Permit 19010899 |
| Permit Number |
19010899 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-08 17:55:41 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF THE MANUFACTURER'S SPECIFICATIONS | | | FOR THE POOL PUMP. FBC 107.2.1 | | | | | | 2) PROVIDE TWO SETS OF TOTAL DYNAMIC HEAD CALCULATIONS | | | FOR THIS POOL. FBC-R4501.6.3 | | | | | | 3) THE PUMP CURVE ON THE PLANS SHOWS THE FLOW RATE AS | | | 98 GPM WITH A TDH OF 38 FT AT 3450 RPM. THE ANSI 15 | | | CHART SHOWS THE HIGH SPEED FLOW RATE AS 98 GPM WITH A | | | TDH OF 20 FT. PLEASE CLARIFY. FBC 107.2.1 |
|