| 2019-02-06 14:03:05 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19010898 |
| | REVIEWED: FEBRUARY 5, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1. 109.3 FBC[AMENDED] THE VALUE APPEARS LOW FOR THE |
| | AMOUNT OF WORK BEING PERFORMED. |
| | PLEASE PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO |
| | SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT |
| | APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL COST OF |
| | WORK. PLEASE ADJUST FEE AT FRONT DESK AND PAY ADJUSTED |
| | PERMIT REVIEW FEE AT TIME OF RE-SUBMITTAL. |
| | |
| | 2. R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. EXCEPTIONS: |
| | |
| | R314.3 FBC[R] LOCATION. SMOKE ALARMS SHALL BE INSTALLED |
| | IN THE FOLLOWING LOCATIONS: |
| | A. IN EACH SLEEPING ROOM. |
| | B. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | C. SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET |
| | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A |
| | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS |
| | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY |
| | SECTION R314.3. |
| | |
| | NOTE: WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED |
| | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |