| Plan Review Notes For Permit 19010816 |
| Permit Number |
19010816 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-01-23 15:44:27 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PLEASE INDICATE WICH UNIT WERE USED FOR INTERIOR | | | SPACE DIMENSION (E.I FEET; INCH). FBC 107 | | | | | | 2. PLEASE INDICATE EXISTING AND PROPOSED LOCATION OF | | | THE PLUMBING FIXTURES. FBC 107 | | | | | | 3. PROVIDE WALL CONSTRUCTION DETAILS. NEW WALL | | | CONSTRUCTION MUST MEET THE REQUIREMENTS OF FBC | | | RESIDENTIAL CHAPTER 6. | | | | | | 4. ONE COPY OF EXISTING FLOOR PLAN AND ONE COPY OF | | | PROPOSED FLOOR PLAN WERE SUBMITTED. PLEASE PROVIDE A | | | MINIMUM OF TWO COPIES FOR ANY CONSTRUCTION DOCUMENT | | | SUBMITTED. | | | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL | | | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL | | | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT | | | APPLICATION. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. |
|