Plan Review Notes
Plan Review Notes For Permit 19010813
Permit Number 19010813
Review Stop B
Sequence Number 1
Notes
Date Text
2019-02-01 17:33:57REVISION - PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE INCREASE IN HEIGHT OF THE NETTING POLES FROM
 150' ABOVE GRADE TO 160' ABOVE GRADE IS REQUIRED TO BE
 APPROVED BY THE PALM BEACH COUNTY AIRPORT AND THE
 CITY'S ZONING DEPARTMENT.
  
 2) THE WINDLOAD ANALYSIS THAT WAS SUBMITTED HAS THE
 VULT WIND SPEED AS 150 MPH AND BUILDING RISK CATEGORY
 II. THE NETTING POLES SHOULD BE CLASSIFIED AS RISK
 CATEGORY I. THIS PROJECT IS LOCATED BETWEEN THE 160 MPH
 AND THE 150 MPH CONTOUR LINES ON THE WIND SPEED MAP FOR
 RISK CATEGORY I. THE WIND SPEED FOR THIS PROJECT
 LOCATION SHOULD BE 155 MPH VULT. 2014 FBC SECTION
 1604.5 & 1609.1 AND ASCE 7 - 10
  
 3) SHEET S5.2 OF THE PLANS HAS THE CORRECT BUILDING
 RISK CATEGORY, HOWEVER, THE VULT WIND SPEED IS
 INCORRECTLY SPECIFIED AS 150 MPH. THE WIND SPEED FOR
 THIS PROJECT LOCATION SHOULD BE 155 MPH VULT. 2014 FBC
 SECTION 1604.5 & 1609.1 AND ASCE 7 - 10.
  
 4) ON SHEET S5.2, THE REINFORCING STEEL AND CONCRETE
 NOTES SPECIFY ACI 318-05. THIS PROJECT IS PERMITTED
 UNDER THE 2014 FLORIDA BUILDING CODE WHICH REFERENCES
 THE 2011 EDITION OF ACI 318 (ACI 318-11). FBC CHAPTER
 35
  
 5) ON SHEET S5.2, THE STRUCTURAL STEEL NOTES SPECIFY
 AISC 360-05. THIS PROJECT IS PERMITTED UNDER THE 2014
 FLORIDA BUILDING CODE WHICH REFERENCES THE 2010 EDITION
 OF AISC 360 (AISC 360-10). FBC CHAPTER 35
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  