| Date |
Text |
| 2019-01-28 12:30:05 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19010744 |
| | ADD: 1701S. FLAGLER DR. APT.: 303 |
| | CONT: AOA CONSTRUCTION LLC |
| | TEL: 561-660-3504 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 28/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE THE SUBMITTED PERMIT APPLICATION WAS |
| | SUBMITTED ELECTRONICALLY, A PAPER ORIGINAL WILL BE |
| | REQUIRED BEFORE PERMIT ISSUANCE WITH BOTH THE OWNER AND |
| | CONTRACTOR SIGNATURES AND NOTARIZED. |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, SECTION 105.3 APPLICATION FOR PERMIT. |
| | |
| | 2) PLEASE NOTE THE WINDLOAD CHART SUBMITTED FROM |
| | ENGINEERING EXPRESS, FRANK BENNARDO P. E. IS A PAPER |
| | COPY SCANNED INTO THE COMPUTER, THE DIGITAL SEAL INFO |
| | IS NOT AN ORIGINAL ELECTRONIC SIGNATURE AND SEAL, IT |
| | CANNOT BE OPENED AND VERIFIED. |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 3) THE SUBMITTED DOCUMENT ILLUSTRATION CHAUDRIC DOES |
| | NOT STATE WHO THE AUTHOR IS OF THIS DOCUMENT. PLEASE |
| | SHOW COMPLIANCE WITH 2017 FLORIDA BUILDING CODE W 2017 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.2 |
| | CERTIFICATIONS BY CONTRACTORS AUTHORIZED UNDER THE |
| | PROVISIONS OF SECTION 489.115 FLORIDA STATUTES, SHALL |
| | BE CONSIDERED EQUIVALENT TO SEALED PLANS AND |
| | SPECIFICATIONS BY A PERSON LICENSED UNDER CHAPTER 471, |
| | FLORIDA STATUTES, OR CHAPTER 481 FLORIDA STATUTES, BY |
| | LOCAL ENFORCEMENT AGENCIES FOR PLANS REVIEW FOR |
| | PERMITTING PURPOSES RELATING TO COMPLIANCE WITH THE |
| | WIND-RESISTANCE PROVISIONS OF THE CODE OR ALTERNATE |
| | METHODOLOGIES APPROVED BY THE FLORIDA BUILDING |
| | COMMISSION FOR ONE AND TWO-FAMILY DWELLINGS. LOCAL |
| | ENFORCEMENT AGENCIES MAY RELY UPON SUCH CERTIFICATION |
| | BY CONTRACTORS THAT THE PLANS AND SPECIFICATIONS |
| | SUBMITTED CONFORM TO THE REQUIREMENTS OF THE CODE FOR |
| | WIND RESISTANCE. UPON GOOD CAUSE SHOWN, LOCAL |
| | GOVERNMENT CODE ENFORCEMENT AGENCIES MAY ACCEPT OR |
| | REJECT PLANS SEALED BY PERSONS LICENSED UNDER CHAPTERS |
| | 471,481 OR 489, FLORIDA STATUTES. |
| | |
| | 4) THE SECOND ISSUE WITH THE SUBMITTED DOCUMENT |
| | ILLUSTRATION CHAUDRIC IS THAT IT DOES NOT PROVIDE WHERE |
| | THIS UNIT IS COMPARED WITH THE OVERALL CONFIGURATION OF |
| | THE BUILDING IF THE UNIT IS TO BE CONSIDERED AS AN |
| | INTERIOR ZONE (4) OR AN END ZONE (5). 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 5) THE WINDOW AND DOOR SCHEDULE INDICATES THE OPENING |
| | SIZE OF THE OVERALL OPENING SIZE BUT NOT THE PANEL |
| | SIZE, EXAMPLE THE SUBMITTED NOA EGS INTERNATIONAL |
| | ALUMINUM SLIDING DOORS L.M.I. 17-1218.22 ON PAGE 5 OF |
| | 11 NO ONE HAS IDENTIFIED THE PANEL WIDTH, HEIGHT, TYPE |
| | OF GLAZING, IF REINFORCEMENT IS REQUIRED OR NOT, NOR |
| | THE SILL HEIGHT WHICH LIMITS THE ALLOWABLE PSF. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 6) THE SUBMITTED MIAMI-DADE NOA 17-0731.06 HAS THE SAME |
| | PROBLEM. NO ONE HAS IDENTIFIED THE OVERALL WINDOW |
| | HEIGHT, WIDTH, AND TYPE OF GLASS NOR THE ASSOCIATED |
| | PRESSURES. NOTE THIS REPORT DOES REQUIRE A SEPARATE |
| | MIAMI-DADE NOA FOR MULTIPLE USE OF WINDOWS WITHIN THE |
| | SAME OPENING. PAGE 7 OF 9 IN THE REPORT INDICATES THE |
| | TYPE OF FASTENERS, BUCKS AND SPACING, AGAIN NO ONE HAS |
| | TAKEN RESPONSIBILITY FOR IDENTIFYING THE TYPE OF |
| | FASTENER. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 7) THE SUBMITTED MIAMI-DADE NOA 17-0717.02 FOR MULLIONS |
| | IS A 22 PAGE REPORT. AGAIN AS IN THE LAST 2 COMMENTS, |
| | NO ONE HAS TAKEN THE RESPONSIBILITY FOR THE TRIBUTARY |
| | AREA THE MULLION IS GOING TO CARRY, THE PRESSURES, |
| | MULLION CONFIGURATION, TYPE OF ANCHORS, IF THE MULLION |
| | IS TO REQUIRE REINFORCEMENT OR NOT. . 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 8) PLEASE NOTE THAT WHEN THIS BUILDING WAS BUILT IT WAS |
| | COMMON TO INSTALL BEVELED WINDOW AND DOOR BUCKS. THE |
| | CODE DOES NOT ALLOW THAT ANYMORE. PLEASE PROVIDE A BUCK |
| | DETAIL AND ANCHORING SCHEDULE FOR BOTH THE WINDOWS AND |
| | SLIDING GLASS DOORS. SHOW COMPLIANCE WITH THE 2017 |
| | FBC-B SECTION: |
| | 1703.4.1 RESEARCH AND INVESTIGATION. SUFFICIENT |
| | TECHNICAL DATA SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL TO SUBSTANTIATE THE PROPOSED USE OF ANY |
| | PRODUCT, MATERIAL OR ASSEMBLY. IF IT IS DETERMINED THAT |
| | THE EVIDENCE SUBMITTED IS SATISFACTORY PROOF OF |
| | PERFORMANCE FOR THE USE INTENDED, THE BUILDING OFFICIAL |
| | SHALL APPROVE THE USE OF THE PRODUCT, MATERIAL OR |
| | ASSEMBLY SUBJECT TO THE REQUIREMENTS OF THIS CODE. THE |
| | COSTS, REPORTS AND INVESTIGATIONS REQUIRED UNDER THESE |
| | PROVISIONS SHALL BE PAID BY THE OWNER OR THE OWNER?S |
| | AUTHORIZED AGENT. |
| | |
| | 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |