| Plan Review Notes For Permit 19010730 |
| Permit Number |
19010730 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-03-13 08:51:52 | PLUMBING APPROVED WITH PROVISO: | | | | | | 1) ANY AND ALL WORK COVERED UP SHALL BE OPENED FOR | | | INSPECTION AND INCLUDES BUT LIMITED TO. SHOWER WET | | | WALLS, SHOWER PAN, CLOTHS WASHER AND ANY OTHER AREA | | | THAT NEW PIPING IS IN. FBC 110.3 | | | | | | 2 ANY AND ALL THROUGH FLOOR PENETRATIONS SHALL BE | | | SEALED WITH MATERIALS COMPLYING WITH THE FBC CHAPTER 7 | | | FIRE AND SMOKE AND FBC ENERGY CODE IN FULL. RATED | | | ASSEMBLY FOR SAID PENETRATIONS SHALL BE INCORPORATED | | | INTO THE PLANS BY A APPROVED REVISION PRIOR TO THE 1ST | | | INSPECTION. FBC 107.2.1. DOCUMENTS SHALL BE SIGNED AND | | | SEAL BY DESIGN PROFESSIONAL OF RECORD. FBC 107.1 | | | | | | 3) PLUMBING ISOMETRIC HAS BEEN RED LINE TO MEET FBC | | | PLUMBING CODE. | | | | | | 4) HAMMER ARRESTORS SHALL BE USED AT ALL QUICK CLOSING | | | VALVES. FBC-P 604.9 | | | | | | 5) SHOWER PAN SHALL BE PRE-PITCH 1/4" PER FOOT. FBC RES | | | P2709.3 | | | | | | 6) SHOWER AND TUB VALVES SHALL BE PRESSURE BALANCED, | | | THERMOSTATIC AND A HIGH LIMIT OF 120F | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | | | | SAMANTHA HILL | | | CHIEF PLANS EXAMINER | | | 561-805-6724 |
|