| Notes |
| Date |
Text |
| 2019-01-29 14:33:23 | APPROVED | | | PROVISO | | | 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL | | | 2. ROUGH IN WORK WHICH HAS BEEN COVERED SHALL BE OPENED | | | FOR INSPECTION AND INCLUDES, BUT IS NOT LIMITED TO, | | | SHOWER WET WALLS, SHOWER PANS AND THE CLOTHES WASHER. | | | 3. SEE REDLINED RISER DIAGRAM AND FLOOR PLAN ON MEP-1 | | | FOR CLOTHES WASHER SANITARY PIPING. | | | 4. ANY AND ALL THROUGH FLOOR PENETRATIONS SHALL BE | | | SEALED WITH MATERIALS COMPLYING WITH THE REQUIREMENTS | | | OF FBC CHAPTER 7 FIRE & SMOKE PROTECTION FEATURES. | | | RATED ASSEMBLY FOR SAID PENETRATIONS SHALL BE | | | INCORPORATED INTO THE PLANS BY REVISION AND SHALL BE IN | | | PLACE PRIOR TO THE FIRST PLUMBING INSPECTION PER WPB | | | FBC 107.2.1. SAID PENETRATIONS INCLUDE BUT ARE NOT | | | LIMITED TO THE SHOWER DRAIN PENETRATIONS, ESPECIALLY | | | WHERE THE EXISTING BATHTUB WAS REPLACED BY A SHOWER. | | | DOCUMENTS SHALL BE SIGNED BY THE PROFESSIONAL DESIGNER | | | OF RECORD PER WPB FBC 107.1. | | | | | | SINCERELY, | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | 561-805-6715 | | | [email protected] | | | |
|