| Date |
Text |
| 2019-02-05 12:48:46 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19010730 |
| | 2/5/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET MEP-1: THERE ARE GENERAL NOTES ON THE PLAN FOR |
| | MECHANICAL BUT NO SPECIFIC PLAN OR NOTES FOR THE |
| | PROPOSED ALTERATION. PLEASE PROVIDE A COMPLETE SCOPE OF |
| | WORK OUTLINE AND MECHANICAL PLAN THAT SHOWS ALL |
| | ALTERATIONS TO THE EXISTING SYSTEMS INCLUDING A DUCT |
| | LAYOUT PLAN, AC EQUIPMENT SCHEDULE, AND THE RELOCATED |
| | DRYER EXHAUST RUN. PLEASE INCLUDE AN AC CHANGEOUT FORM |
| | IF THE SYSTEM IS BEING REPLACED- SECTION 107.2.1 WPB. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER, |
| | THE RANGE, AND MICROWAVE- SECTIONS 504.1, AND 505.1 FBC |
| | M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |