| 2019-01-22 10:06:41 | PERMIT # 19010721 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | APPROVED PROVISO: |
| | |
| | A FINAL FIRE INSPECTION MAY BE REQUIRED PRIOR TO THE |
| | EVENT DATE TO ENSURE COMPLIANCE WITH ALL APPLICABLE |
| | FIRE CODES. |
| | |
| | 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE |
| | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. |
| | |
| | 2) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM |
| | BUILDING STRUCTURES. |
| | |
| | 3) DUE TO THE MAIN EVENT TENT EXCEEDING 1,200 SQUARE |
| | FEET, THE TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL |
| | TYPE, OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT |
| | SIGNS ARE REQUIRED. |
| | |
| | 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS |
| | LOCATIONS. |
| | |
| | 5) GENERATORS AND OTHER INTERNAL COMBUSTION POWER |
| | SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 |
| | FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR |
| | ENCLOSURE. |
| | |
| | 6) THE ASSEMBLY TENT SHALL HAVE THE SEATING ARRANGED IN |
| | A MANNER THAT COMPLIES WITH THE AISLE AND AISLEWAY |
| | REQUIREMENTS AS LISTED UNDER NFPA 101: 12.2.5 |
| | (ARRANGEMENT OF MEANS OF EGRESS). |
| | |
| | 7) THE OCCUPANT LOAD FOR THE ASSEMBLY TENT SHALL COMPLY |
| | WITH THE OCCUPANT LOAD FACTOR AS LISTED UNDER NFPA 101: |
| | CHAPTER 7, TABLE 7.3.1.2. MORE SPECIFICALLY, ASSEMBLY |
| | USE: LESS CONCENTRATED USE, WITHOUT FIXED SEATING - 15 |
| | SQ FT/PERSON. |
| | |
| | |